SIEMENS
6/4
Siemens KT 10.1 · 2016
6
■
Technical specifications
(continued)
SITOP modular
1-phase, 24 V DC
Input current
• at rated input voltage 120 V
2.1 A
4 A
4.6 A
15 A
• at rated input voltage 230 V
1.2 A
1.9 A
2.5 A
8 A
Switch-on current limiting (+25 °C),
max.
10 A
10 A
20 A
125 A
I²t, max.
0.2 A²·s
0.3 A²·s
5 A²·s
26 A²·s
Built-in incoming fuse
T 3.15 A (not accessible)
T 6.3 A (not accessible)
Yes
Yes
Protection in the mains power input
(IEC 898)
Recommended miniature
circuit breaker at 1-phase
operation: from 6 A (10 A)
characteristic C (B); required
at 2-phase operation:
circuit breaker 2-pole
connected or circuit breaker
3RV2011-1EA10 (setting
3.8 A) or 3RV2711-1ED10
(UL 489) at 230 V;
3RV2011-1DA10 (setting 3 A)
or 3RV2711-1DD10 (UL 489)
at 400/500 V
Recommended miniature
circuit breaker at 1-phase
operation: from 6 A (10 A)
characteristic C (B); required
at 2-phase operation:
circuit breaker 2-pole
connected or circuit breaker
3RV2011-1EA10 (setting
3.8 A) or 3RV2711-1ED10
(UL 489) at 230 V;
3RV2011-1DA10 (setting 3 A)
or 3RV2711-1DD10 (UL 489)
at 400/500 V
Recommended miniature
circuit breaker at 1-phase
operation: 10 A characteristic
C; required at 2-phase
operation: circuit breaker
2-pole connected or circuit
breaker 3RV2711-1HD10
(UL 489) at 120 V or
3RV2711-1ED10 (UL 489)
at 230 V
Recommended miniature
circuit breaker at 1-phase
operation: 20 A characteristic
C; required at 2-phase
operation: circuit breaker
2-pole connected or circuit
breaker 3RV2421-4BA10
(120 V) or 3RV2411-1JA10
(230 V)
Output
Output
Controlled, isolated
DC voltage
Controlled, isolated
DC voltage
Controlled, isolated
DC voltage
Controlled, isolated
DC voltage
Rated voltage
V
out
DC
24 V
24 V
24 V
24 V
Total tolerance, static ±
3 %
3 %
3 %
3 %
Static mains compensation, approx.
0.1 %
0.1 %
0.1 %
0.1 %
Static load balancing, approx.
0.2 %
0.3 %
0.3 %
0.1 %
Residual ripple peak-peak, max.
50 mV
50 mV
100 mV
100 mV
Residual ripple peak-peak, typ.
-
-
80 mV
60 mV
Spikes peak-peak, max.
(bandwidth: 20 MHz)
200 mV
200 mV
200 mV
200 mV
Spikes peak-peak, typ.
(bandwidth: 20 MHz)
-
-
100 mV
120 mV
Adjustment range
24…28.8 V
24…28.8 V
24…28.8 V
24…28.8 V
产品function
Output voltage adjustable
Yes
Yes
Yes
Yes
Output voltage setting
via potentiometer;
max. 120 W
via potentiometer;
max. 240 W
via potentiometer
via potentiometer
Status display
Green LED for 24 V OK
Green LED for 24 V OK
Green LED for 24 V OK
Green LED for 24 V OK
Signaling
Relay contact (NO contact,
rating 60 V DC/ 0.3 A) for
"24 V OK"
Relay contact (NO contact,
rating 60 V DC/ 0.3 A) for
"24 V OK"
Relay contact (NO contact,
rating 60 V DC/ 0.3 A) for
"24 V OK"
via signaling module
(6EP1961-3BA10)
On/off behavior
Overshoot of
V
out
approx.
3 %
Overshoot of
V
out
approx.
3 %
No overshoot of
V
out
(soft start)
Overshoot of
V
out
approx.
3 %
Startup delay, max.
1 s
1 s
0.25 s
0.1 s
Voltage rise, typ.
30 ms
70 ms
50 ms
50 ms
Rated current value
I
out rated
5 A
10 A
20 A
40 A
Current range
0 ... 5 A
0 ... 10 A
0 ... 20 A
0 ... 40 A
• Note
As of
U
a
>24 V: 4% [
I
a
]/V [
U
a
];
at
U
e
<100 V/<200 V:
80%
I
a rated
+60 ... +70 °C: Derating
2%/K; as of
U
a
>24 V:
4% [
I
a
]/V [
U
a
];
at
U
e
<100 V/<200 V:
80%
I
a rated
+60 ... +70 °C: Derating
3%/K
+60 ... +70 °C: Derating
2.5%/K
Supplied active power typical
120 W
240 W
480 W
960 W
Short-term overload current
• at short-circuit during operation
typical
15 A
30 A
60 A
120 A
Duration of overloading capability
for excess current
• at short-circuit during operation
25 ms
25 ms
25 ms
25 ms
Constant overload current
• on short-circuiting during the
start-up typical
6 A
12A
30 A
46 A
Parallel switching for enhanced
performance
Yes; switchable
characteristic
Yes; switchable
characteristic
Yes; switchable
characteristic
Yes; switchable
characteristic
Numbers of parallel switchable units
for enhanced performance
2
2
2
2
Article number
6EP3333-8SB00-0AY0
6EP3334-8SB00-0AY0
6EP1336-3BA10
6EP1337-3BA00
产品
SITOP PSU8200
SITOP PSU8200
SITOP PSU8200
SITOP PSU100M
Power supply, type
24 V/5 A
24 V/10 A
24 V/20 A
24 V / 40
© Siemens AG 2016