SIEMENS
9/12
Siemens KT 10.1 · 2016
9
■
Technical specifications
(continued)
Special designs, special uses
High degree of protection
1-phase, 24 V DC
(SITOP PSU100P, IP67)
On/off behavior
Overshoot of
V
out
< 3 %
Overshoot of
V
out
< 3 %
Startup delay, max.
1.5 s
1.5 s
Voltage rise, typ.
22 ms
23 ms
Voltage increase time of the output voltage
maximum
100 ms
100 ms
Rated current value
I
out rated
5 A
8 A
Current range
0 ... 5 A
0 ... 8 A
Supplied active power typical
133W
206 W
Short-term overload current
• on short-circuiting during the start-up typical
20 A
30 A
•在short-circuit during operation typical
20 A
30 A
Duration of overloading capability for excess
当前的
• on short-circuiting during the start-up
50 ms
50 ms
•在short-circuit during operation
50 ms
50 ms
Parallel switching for enhanced performance
Yes; Symmetric wiring required
Yes; Symmetric wiring required
Numbers of parallel switchable units for
enhanced performance
2
2
Efficiency
Efficiency at
V
out rated
, I
out rated
, approx.
90 %
93.6 %
Power loss at
V
out rated
, I
out rated
, approx.
12.9 W
13.1 W
Closed-loop control
Dynamic mains compensation
(
V
in rated
±15 %), max.
0.2 %
0.2 %
Dynamic load smoothing (
I
out
50/100/50 %),
U
out
± typ.
1 %
1 %
Setting time maximum
2 ms
2 ms
Protection and monitoring
Output overvoltage protection
< 29 V
< 29 V
Current limitation, typ.
5.5 A
9 A
Property of the output Short-circuit proof
Yes
Yes
Short-circuit protection
Electronic shutdown, automatic restart
Electronic shutdown, automatic restart
Enduring short circuit current RMS value
• maximum
6 A
9 A
• typical
5 A
8 A
Overload/short-circuit indicator
Red LED flashing for "overload/short-circuit"
Red LED flashing for "overload/short-circuit"
Safety
Primary/secondary isolation
Yes
Yes
Galvanic isolation
Safety extra-low output voltage
U
out
acc. to
EN 60950-1 and EN 50178
Safety extra-low output voltage
U
out
acc. to
EN 60950-1 and EN 50178
Protection class
Class I
Class I
Leakage current
• maximum
3.5 mA
3.5 mA
• typical
1 mA
1 mA
CE mark
Yes
Yes
UL/cUL (CSA) approval
cULus-Listed (UL 508, CSA C22.2 No. 107.1)
cULus-Listed (UL 508, CSA C22.2 No. 107.1)
Explosion protection
No
No
FM approval
-
-
CB approval
No
No
Marine approval
No
No
Degree of protection (EN 60529)
IP67, enclosure type 4 indoor
IP67, enclosure type 4 indoor
EMC
Emitted interference
EN 55022 Class B
EN 55022 Class B
Supply harmonics limitation
EN 61000-3-2
EN 61000-3-2
Noise immunity
EN 61000-6-2
EN 61000-6-2
Article number
6EP1333-7CA00
6EP1334-7CA00
产品
SITOP PSU100P
SITOP PSU100P
Power supply, type
24V/5 A
24V/8 A
© Siemens AG 2016