SIEMENS
8/9
Siemens KT 10.1 · 2016
8
SITOP in the SIMATIC Design
1-phase, 24 V DC (for S7-1200)
■
Overview
In terms of design and functionality, the SIMATIC PM 1207
single-phase load power supply (PM = power module) with
automatic range selection of the input voltage is an optimal
match to the SIMATIC S7-1200 PLC. It provides the supply to
CPUs with 24 V input as well as to signal modules, and to 24 V
loads connected to the modules. Comprehensive certifications,
such as UL, ATEX and GL facilitate universal use.
■
Design
•
The load current supplies are directly fastened to the S7-1200
mounting rail (without connection to the backplane bus) and
can be mounted directly to the left of the CPU (no installation
clearance required)
•
LED for status indicator "24 V OK"
•
Two 24 V DC output terminals for connection of 24 V
consumers
■
Function
•
Connection to all 1-phase networks (120 V AC/230 V AC)
through automatic range switching
•
Short-term power failure backup
•
Parallel connection of two load current supplies for enhanced
performance
■
Technical specifications
Article number
6EP1332-1SH71
产品
S7-1200 PM1207
Power supply, type
24 V/2.5 A
Input
Input
1-phase AC
Supply voltage
• 1 at AC Rated value
120 V
• 2 at AC Rated value
230 V
• Note
Automatic range selection
Input voltage
• 1 at AC
85 ... 132 V
• 2 at AC
176 ... 264 V
Wide-range input
No
Overvoltage resistance
2.3 ×
V
in rated
, 1.3 ms
Mains buffering at
I
out rated
, min.
20 ms; at
V
in
= 93/187 V
Rated line frequency 1
50 Hz
Rated line frequency 2
60 Hz
Rated line range
47 ... 63 Hz
Input current
• at rated input voltage 120 V
1.2 A
• at rated input voltage 230 V
0.67 A
Switch-on current limiting (+25 °C),
max.
13 A
Duration of inrush current limiting at
25 °C
• maximum
3 ms
I²t, max.
0.5 A²·s
Built-in incoming fuse
T 3,15 A/250 V (not accessible)
Protection in the mains power input
(IEC 898)
Recommended miniature circuit
breaker: 16 A characteristic B or
10 A characteristic C
Output
Output
Controlled, isolated DC voltage
Rated voltage
V
out
DC
24 V
Total tolerance, static ±
3 %
Static mains compensation, approx.
0.1 %
Static load balancing, approx.
0.2 %
Residual ripple peak-peak, max.
150 mV
Spikes peak-peak, max.
(bandwidth: 20 MHz)
240 mV
产品function Output voltage
adjustable
No
Output voltage setting
-
Status display
Green LED for 24 V OK
On/off behavior
No overshoot of
V
out
(soft start)
Startup delay, max.
6 s; 2 s at 230 V, 6 s at 120 V
Voltage rise, typ.
10 ms
Rated current value
I
out rated
2.5 A
Current range
0 ... 2.5 A
Supplied active power typical
60 W
Short-term overload current
• on short-circuiting during the
start-up typical
6 A
• at short-circuit during operation
typical
6 A
Duration of overloading capability
for excess current
• on short-circuiting during the
start-up
100 ms
• at short-circuit during operation
100 ms
Parallel switching for enhanced
performance
Yes
Numbers of parallel switchable units
for enhanced performance
2
© Siemens AG 2016