Siemens D 21.4 · 2017
Tools and configuration
Configuration notes
Mechanical configuration of the drive system
13.
■
Configuration
(继续)
Configuration of a drive line-up in chassis format
•
The Motor Modules must be positioned to the left or right of the
Line Module with decreasing rated currents (i.e. the Motor
额定电流最高电流的模块位于旁边
线路模块,而电机模块具有最低额定值
current is at the end on the left or right). You must ensure that
直流链路的电缆/母线符合当前携带
capacity requirements for all connected Motor Modules.
•
The inductance of the DC link busbars must be low, achieved,
for example, by arranging the bars as close as possible in
并行,但观察所需的爬电距离和
空气差距。
•
控制单元配置是灵活的。下列
configuration options are possible:
- 在线模块的左侧“对接”
-
Direct mounting next to the drive line-up on a mounting plate
-Mounting in other cabinet panels taking into account the
允许的驱动器CLIQ电缆长度
Configuration of a mixed drive line-up in chassis and
booksize formats
一种mixed drive line-up must be configured according to the rules
适用于机箱格式单位。图书化格式中的电机模块
可以通过方式连接到更高级别的直流链路母线
of DC link rectifier adapters. There are two possible connection
options - A and B. With A, each Motor Module in booksize format
使用相应的DC链路整流器适配器连接。和
b,图书化格式中的电机模块连接到一个
另一个和内部直流链路母线和直流链路整流器
适配器用于最后一个电机模块以使连接 -
到更高级别的直流链路母线。在后一种情况下,DC
链接整流器适配器必须连接到最后一个电机模块
在线的右侧。关于安排
modules with different current ratings, the guidelines specified
还在“书籍中的驱动器阵容中的配置”下
适用于混合驱动线。
理想情况下,高级直流链路母线的整个长度可以
尺寸为线路模块的额定直流链路电流。
The busbars are then protected by the line fuses at the infeed
结尾。
如果降低了直流链路母线或布线的横截面,
该分支必须设计为短路。诅咒
连接到电机模块的租金限制机制
减少横截面的分支,然后防止它
装载。减少汇流或者是不可取的cables down to
强制性最小截面。没有额外的过载
protection (fuse) is required on the assumption that overloading
cannot occur as a result of cable damage on the cable route to
电机模块和电路分支受到保护
电机模块过载。
横截面显着减少,或者
电路设计并不固有的短路,分支保险丝
must be installed at the beginning of the section with reduced
横截面以保护直流链路连接 -
volved. In the event of a fault, the fuse must be capable of inter-
rupting DC fault currents; other types of miniature circuit breaker
不合适。
供应系统中的选项(a)分支保险丝的分配
接地中性(TN系统)。计算基于
假设这一点
τ
=
L / R.
<
10 ms适用于时间常数
τ
in the DC fault circuit and that the fault current is interrupted by
最多1秒后的保险丝。
Motor
模块
Motor
模块
积极的
界面
模块
Motor
模块
Motor
模块
Motor
模块
积极的
Line
模块
high
力量
低的
力量
high
力量
低的
力量
DC interface
G_D211_EN_00022a
一种
B.
high
力量
低的
力量
低的
力量
high
力量
G_D211_EN_00134a
Motor
模块
Motor
模块
Motor
模块
Motor
模块
Motor
模块
Motor
模块
积极的
界面
模块
积极的
Line
模块
©Siemens AG 2017