SIEMENS
7/241
Siemens D 21.4 · 2017
SINAMICS S120 drive system
Blocksize format
Air-cooled Power Modules in blocksize format
7
PM240-2 Power Modules push-through variant
Shield connection kit for Power Modules
The shield connection kit makes it easier to connect the shields
of supply and control cables, provides mechanical strain relief
and thus ensures optimum EMC performance. The shield
connection kit is included in the scope of delivery of PM240-2
Power Modules.
380 ... 480 V 3 AC
4)
(continued)
110
150
205
90
125
178
FSF
6SL3210-1PE32-1UL0
6SL3210-1PE32-1AL0
132
200
250
110
150
205
FSF
6SL3210-1PE32-5UL0
6SL3210-1PE32-5AL0
500 ... 690 V 3 AC
11
10
14
7.5
7,5
11
FSD
6SL3210-1PH21-4UL0
6SL3210-1PH21-4AL0
15
15
19
11
10
14
FSD
6SL3210-1PH22-0UL0
6SL3210-1PH22-0AL0
18.5
20
23
15
15
19
FSD
6SL3210-1PH22-3UL0
6SL3210-1PH22-3AL0
22
25
27
18.5
20
23
FSD
6SL3210-1PH22-7UL0
6SL3210-1PH22-7AL0
30
30
35
22
25
27
FSD
6SL3210-1PH23-5UL0
6SL3210-1PH23-5AL0
37
40
42
30
30
35
FSD
6SL3210-1PH24-2UL0
6SL3210-1PH24-2AL0
45
50
52
37
40
42
FSE
6SL3210-1PH25-2UL0
6SL3210-1PH25-2AL0
55
60
62
45
50
52
FSE
6SL3210-1PH26-2UL0
6SL3210-1PH26-2AL0
75
75
80
55
60
62
FSF
6SL3210-1PH28-0UL0
6SL3210-1PH28-0AL0
90
100
100
75
75
80
FSF
6SL3210-1PH31-0UL0
6SL3210-1PH31-0AL0
110
100
115
90
100
100
FSF
6SL3210-1PH31-2UL0
6SL3210-1PH31-2AL0
132
125
142
110
100
115
FSF
6SL3210-1PH31-4UL0
6SL3210-1PH31-4AL0
Type rating
1)
Rated
output
current
I
rated
5)
Power based
on the
base-load current
3)
Base-load
current
I
H
3)
Frame size
PM240-2 Power Module
push-through variant
without
integrated line filter
PM240-2 Power Module
push-through variant
with
integrated line filter
class A
kW
hp
A
kW
hp
A
(Frame size)
Article No.
Article No.
200 ... 240 V 1 AC/3 AC
0.75
1
3.9
0.55
0.75
3
FSA
6SL3211-1PB13-8UL0
6SL3211-1PB13-8AL0
2.2
3
10.4
1.5
2
7.4
FSB
6SL3211-1PB21-0UL0
6SL3211-1PB21-0AL0
4
5
17.5
3
4
13.6
FSC
6SL3211-1PB21-8UL0
6SL3211-1PB21-8AL0
380 ... 480 V 3 AC
3
4
7.7
2.2
7.5
5.9
FSA
6SL3211-1PE18-0UL1
6SL3211-1PE18-0AL1
7.5
10
18
5.5
7.5
13.2
FSB
6SL3211-1PE21-8UL0
6SL3211-1PE21-8AL0
15
20
32
11
15
26
FSC
6SL3211-1PE23-3UL0
6SL3211-1PE23-3AL0
Type rating
1)
Rated
output
current
I
rated
2)
Power based
on the
base-load current
3)
Base-load
current
I
H
3)
Frame size
PM240-2 Power Module
standard variant
without
integrated line filter
PM240-2 Power Module
standard variant
with
integrated line filter
class A
kW
hp
A
kW
hp
A
(Frame size)
Article No.
Article No.
1)
类型评级基于额定输出电流
I
rated
. The rated output
current
I
rated
is based on the duty cycle for low overload (LO).
2)
The rated output current
I
rated
is based on the duty cycle for low overload
(LO). These current values are valid for 200 V, 400 V or 690 V and are
specified on the rating plate of the Power Module.
3)
The base-load current
I
H
is based on the duty cycle for high overload
(HO).
4)
SIPLUS components for extreme requirements are available. Additional
information is available on the Internet at
/siplus-drives
5)
The rated output current
I
rated
is based on the duty cycle for low overload
(LO). These current values are valid for 200 V or 400 V and are specified
on the rating plate of the Power Module.
■
Selection and ordering data
(continued)
© Siemens AG 2017