SIEMENS
7/139
Siemens D 21.4 · 2017
SINAMICS S120 drive system
Chassis format
Air-cooled Smart Line Modules in chassis format
7
■
Technical specifications
(continued)
Line voltage 500 ... 690 V 3 AC
Smart Line Modules
6SL3330-6TG35-5AA3
6SL3330-6TG38-8AA3
6SL3330-6TG41-2AA3
6SL3330-6TG41-7AA3
Rated power
• At
I
rated DC
(50赫兹690 V)
kW
450
710
1000
1400
• At
I
H DC
(50赫兹690 V)
kW
405
665
885
1255
• At
I
rated DC
(50赫兹500 V)
kW
320
525
705
995
• At
I
H DC
(50赫兹500 V)
kW
295
480
640
910
• At
I
rated DC
(60 Hz 575 V)
hp
500
790
1115
1465
• At
I
H DC
(60 Hz 575 V)
hp
450
740
990
1400
DC link current
• Rated current
I
rated DC
A
550
900
1200
1700
• Base-load current
I
H DC
1)
A
490
800
1068
1513
• Maximum current
I
max DC
A
825
1350
1800
2550
Infeed/regenerative feedback current
• Rated current
I
rated I
A
463
757
1009
1430
• Maximum current
I
max I
A
694
1135
1513
2145
Current demand
• 24 V DC auxiliary power supply
A
1.35
1.4
1.5
1.7
• 500 V AC
A
1.3
2.9
4.3
4.3
• 690 V AC
A
0.94
2.1
3.1
3.1
DC link capacitance
• Smart Line Module
μ
F
5600
7400
11100
14400
• Drive line-up, max.
μ
F
28000
29600
44400
57600
Power loss, max.
2)
• At 50 Hz 690 V
kW
4.3
6.5
12.0
13.8
• At 60 Hz 575 V
kW
4.3
6.5
12.0
13.8
Cooling air requirement
m
3
/s (ft
3
/s)
0.36 (12.7)
0.78 (27.5)
1.08 (38.1)
1.08 (38.1)
Sound pressure level
L
pA
(1米)50/60 Hz
dB
69/73
70/73
70/73
70/73
Line connection
U1, V1, W1
Flat connector for
M10 screw
Flat connector for
M12 screw
Flat connector for
M12 screw
Flat connector for
M12 screw
• Conductor cross section, max. (IEC)
mm
2
2 × 240
4 × 240
6 × 240
6 × 240
DC link connection
DCP, DCN
M10 screw
4 × hole for M12
4 × hole for M12
4 × hole for M12
• Conductor cross section, max. (IEC)
mm
2
2 × 240
Busbar
Busbar
Busbar
PE connection
Hole for M10
- - - - - -
- - - - - -
- - - - - -
• Conductor cross section, max. (IEC)
mm
2
2 × 240
- - - - - -
- - - - - -
- - - - - -
PE1/GND connection
- - - - - -
M12 screw
M12 screw
M12 screw
• Conductor cross section, max. (IEC)
mm
2
- - - - - -
240
240
240
PE2/GND connection
- - - - - -
2 × M12 screw
2 × M12 screw
2 × M12 screw
• Conductor cross section, max. (IEC)
mm
2
- - - - - -
2 × 240
2 × 240
2 × 240
Cable length, max.
3)
• Shielded
m (ft)
2250 (7382)
2750 (9023)
2750 (9023)
2750 (9023)
• Unshielded
m (ft)
3375 (11073)
4125 (13534)
4125 (13534)
4125 (13534)
Degree of protection
IP00
IP00
IP00
IP00
Dimensions
• Width
mm (in)
310 (12.2)
503 (19.8)
704 (27.7)
704 (27.7)
• Height
mm (in)
1413 (55.6)
1475 (58.1)
1480 (58.3)
1480 (58.3)
• Depth
mm (in)
550 (21.6)
548 (21.6)
550 (21.6)
550 (21.6)
Weight, approx.
kg (lb)
150 (331)
294 (648)
458 (1010)
458 (1010)
Frame size
GX
HX
JX
JX
Minimum short-circuit current
4)
A
6200
10500
12400
21000
1)
The base-load current
I
H DC
is the basis for a duty cycle of 150 % for 60 s
or
I
max DC
for 5 s with a duty cycle duration of 300 s.
2)
The specified power loss represents the maximum value at 100 % utilization.
The value is lower under normal operating conditions.
3)
Total of all motor cables and DC link. Longer cable lengths for specific
configurations are available on request.
For additional information, please
refer to the SINAMICS Low Voltage Engineering Manual
.
4)
Current required for reliably triggering protective devices.
© Siemens AG 2017