SIEMENS
7/138
Siemens D 21.4 · 2017
SINAMICS S120 drive system
Chassis format
气冷式智能在底盘线模块格式
7
■
Technical specifications
(continued)
Line voltage 380 ... 480 V 3 AC
Smart Line Modules
6SL3330-
6TE35-5AA3
6SL3330-
6TE37-3AA3
6SL3330-
6TE41-1AA3
6SL3330-
6TE41-3AA3
6SL3330-
6TE41-7AA3
Rated power
• At
I
rated DC
(50 Hz 400 V)
kW
250
355
500
630
800
• At
I
H DC
(50 Hz 400 V)
kW
235
315
450
555
730
• At
I
rated DC
(60 Hz 460 V)
hp
385
545
770
970
1230
• At
I
H DC
(60 Hz 460 V)
hp
360
485
695
855
1125
DC link current
• Rated current
I
rated DC
A
550
730
1050
1300
1700
• Base-load current
I
H DC
1)
A
490
650
934
1157
1513
• Maximum current
I
max DC
A
825
1095
1575
1950
2550
Infeed/regenerative feedback current
• Rated current
I
rated I
A
463
614
883
1093
1430
• Maximum current
I
max I
A
694
921
1324
1639
2145
Current demand
• 24 V DC auxiliary power supply
A
1.35
1.35
1.4
1.5
1.7
• 400 V AC
A
1.8
1.8
3.6
5.4
5.4
DC link capacitance
• Smart Line Module
μ
F
8400
12000
16800
18900
28800
• Drive line-up, max.
μ
F
42000
60000
67200
75600
115200
Power loss, max.
2)
• At 50 Hz 400 V
kW
3.7
4.7
7.1
11.0
11.5
• At 60 Hz 460 V
kW
3.7
4.7
7.1
11.0
11.5
Cooling air requirement
m
3
/s (ft
3
/s)
0.36 (12.7)
0.36 (12.7)
0.78 (27.5)
1.08 (38.1)
1.08 (38.1)
Sound pressure level
L
pA
(1 m) at 50/60 Hz
dB
69/73
69/73
70/73
70/73
70/73
Line connection
U1, V1, W1
Flat connector for
M10 screw
Flat connector for
M10 screw
Flat connector for
M12 screw
Flat connector for
M12 screw
Flat connector for
M12 screw
• Conductor cross section, max. (IEC)
mm
2
2 × 240
2 × 240
4 × 240
6 × 240
6 × 240
DC link connection
DCP, DCN
M10 screw
M10 screw
4 × hole for M12
4 × hole for M12
4 × hole for M12
• Conductor cross section, max. (IEC)
mm
2
2 × 240
2 × 240
Busbar
Busbar
Busbar
PE/GND connection
Hole for M10
Hole for M10
- - - - - -
- - - - - -
- - - - - -
• Conductor cross section, max. (IEC)
mm
2
2 × 240
2 × 240
- - - - - -
- - - - - -
- - - - - -
PE1/GND connection
- - - - - -
- - - - - -
M12 screw
M12 screw
M12 screw
• Conductor cross section, max. (IEC)
mm
2
- - - - - -
- - - - - -
240
240
240
PE2/GND connection
- - - - - -
- - - - - -
2 × M12 screw
2 × M12 screw
2 × M12 screw
• Conductor cross section, max. (IEC)
mm
2
- - - - - -
- - - - - -
2 × 240
2 × 240
2 × 240
Cable length, max.
3)
• Shielded
m (ft)
4000 (13124)
4000 (13124)
4800 (15749)
4800 (15749)
4800 (15749)
• Unshielded
m (ft)
6000 (19686)
6000 (19686)
7200 (23623)
7200 (23623)
7200 (23623)
Degree of protection
IP00
IP00
IP00
IP00
IP00
Dimensions
• Width
mm (in)
310 (12.2)
310 (12.2)
503 (19.8)
704 (27.7)
704 (27.7)
• Height
mm (in)
1413 (55.6)
1413 (55.6)
1475 (58.1)
1480 (58.3)
1480 (58.3)
• Depth
mm (in)
550 (21.6)
550 (21.6)
548 (21.6)
550 (21.6)
550 (21.6)
Weight, approx.
kg (lb)
150 (331)
150 (331)
294 (648)
458 (1010)
458 (1010)
Frame size
GX
GX
HX
JX
JX
Minimum short-circuit current
4)
A
6200
9200
10400
16000
21000
1)
The base-load current
I
H DC
is the basis for a duty cycle of 150 % for 60 s
or
I
max DC
for 5 s with a duty cycle duration of 300 s.
2)
The specified power loss represents the maximum value at 100 % utilization.
The value is lower under normal operating conditions.
3)
Total of all motor cables and DC link. Longer cable lengths for specific
configurations are available on request.
For additional information, please
refer to the SINAMICS Low Voltage Engineering Manual
.
4)
Current required for reliably triggering protective devices.
© Siemens AG 2017