SIEMENS
7/127
Siemens D 21.4 · 2017
SINAMICS S120 drive system
Chassis format
Air-cooled Active Line Modules in chassis format
7
■
Technical specifications
(continued)
Line voltage 380 ... 480 V 3 AC
Active Line Modules
6SL3330-
7TE37-5AA3
6SL3330-
7TE38-4AA3
6SL3330-
7TE41-0AA3
6SL3330-
7TE41-2AA3
6SL3330-
7TE41-4AA3
Rated power
• At
I
rated DC
(50 Hz 400 V)
kW
450
500
630
800
900
• At
I
H DC
(50 Hz 400 V)
kW
400
465
545
690
780
• At
I
rated DC
(60 Hz 460 V)
hp
600
700
900
1000
1250
• At
I
H DC
(60 Hz 460 V)
hp
600
700
800
900
1000
DC link current
• Rated current
I
rated DC
A
835
940
1103
1412
1574
• Base-load current
I
H DC
1)
A
700
837
982
1255
1401
• Maximum current
I
max DC
A
1252
1410
1654
2120
2361
Infeed/regenerative feedback current
• Rated current
I
rated I
A
745
840
985
1260
1405
• Maximum current
I
max I
A
1117
1260
1477
1890
2107
Current demand
• 24 V DC auxiliary power supply
A
1.4
1.4
1.5
1.7
1.7
• 400 V AC
A
3.6
3.6
5.4
5.4
5.4
DC link capacitance
• Active Line Module
μ
F
15600
16800
18900
26100
28800
• Drive line-up, max.
μ
F
134400
134400
230400
230400
230400
Power loss, max.
2)
• At 50 Hz 400 V
kW
7.3
7.7
10.1
12.1
13.3
• At 60 Hz 460 V
kW
7.7
8.2
10.8
13.0
14.2
Cooling air requirement
m
3
/s (ft
3
/s)
0.78 (27.5)
0.78 (27.5)
1.08 (38.1)
1.08 (38.1)
1.08 (38.1)
Sound pressure level
L
pA
3)
(1)在50/60 Hz
dB
70/73
70/73
71/73
71/73
71/73
Line connection
U1, V1, W1
Flat connector for
M12 screw
Flat connector for
M12 screw
Flat connector for
M12 screw
Flat connector for
M12 screw
Flat connector for
M12 screw
• Conductor cross section, max. (IEC)
mm
2
4 × 240
4 × 240
6 × 240
6 × 240
6 × 240
DC link connection
DCP, DCN
4 × hole for M12
4 × hole for M12
4 × hole for M12
4 × hole for M12
4 × hole for M12
• Conductor cross section, max. (IEC)
mm
2
Busbar
Busbar
Busbar
Busbar
Busbar
PE1/GND connection
M12 screw
M12 screw
M12 screw
M12 screw
M12 screw
• Conductor cross section, max. (IEC)
mm
2
240
240
240
240
240
PE2/GND connection
2 × M12 screw
2 × M12 screw
3 × M12 screw
3 × M12 screw
3 × M12 screw
• Conductor cross section, max. (IEC)
mm
2
2 × 240
2 × 240
3 × 240
3 × 240
3 × 240
Cable length, max.
4)
• Shielded
m (ft)
3900 (12796)
3900 (12796)
3900 (12796)
3900 (12796)
3900 (12796)
• Unshielded
m (ft)
5850 (19194)
5850 (19194)
5850 (19194)
5850 (19194)
5850 (19194)
Degree of protection
IP00
IP00
IP00
IP00
IP00
维
• Width
mm (in)
503 (19.8)
503 (19.8)
704 (27.7)
704 (27.7)
704 (27.7)
• Height
mm (in)
1475 (58.1)
1475 (58.1)
1480 (58.3)
1480 (58.3)
1480 (58.3)
• Depth
mm (in)
540 (21.3)
540 (21.3)
550 (21.6)
550 (21.6)
550 (21.6)
Weight, approx.
kg (lb)
290 (639)
290 (639)
450 (992)
450 (992)
450 (992)
Frame size
HX
HX
JX
JX
JX
Minimum short-circuit current
5)
A
8800
10400
16000
21000
21000
1)
The base-load current
I
H DC
is the basis for a duty cycle of 150 % for 60 s
or
I
max DC
for 5 s with a duty cycle duration of 300 s.
2)
The specified power loss represents the maximum value at 100 % utilization.
The value is lower under normal operating conditions.
3)
Total sound pressure level of Active Interface Module and Active Line
Module.
4)
Total of all motor cables and DC link. Longer cable lengths for specific
configurations are available on request.
For additional information, please
refer to the SINAMICS Low Voltage Engineering Manual
.
5)
Current required for reliably triggering protective devices.
© Siemens AG 2017