SIEMENS
5/83
Siemens D 31 N · March 2016
SINAMICS G120 standard inverters
0.37 kW to 250 kW (0.5 hp to 400 hp)
Power Modules
5
■
Dimensional drawings
PM240 and PM250 Power Modules, IP20 degree of protection
Principle dimension drawing and drill pattern for PM240 and PM250 Power Modules, degree of protection IP20, with/without integrated line filter class A
Frame
size
Dimensions
in mm
(inches)
Drilling dimensions
in mm
(inches)
Cooling clearance
in mm
(inches)
Mounting
a
(width)
b
(height)
c
(depth)
1)
d
e
f
top/bottom
side
front
With bolts,
nuts and
washers
PM240 Power Modules, degree of protection IP20, with/without integrated line filter class A
FSGX
326
(12.9)
1533
(60.35)
547
(21.6)
125
(4.92)
1506
(59.29)
14.5
(0.57)
250/150
(9.84/5.91)
0
(0)
50
(1.97)
6 x M8
PM250 Power Modules, degree of protection IP20, with/without integrated line filter class A
FSC
189
(7.44)
334
(13.15)
185
(7.28)
167
(6.57)
323
(12.72)
6
(0.24)
125
(4.92)
50
(1.97)
2)
0
(0)
4 × M5
FSD
275
(10.83)
419/512
(16.5/20.16)
204
(8.03)
235
(9.25)
325/419
(12.8/16.5)
11
(0.43)
300
(11.81)
0
(0)
0
(0)
4 × M8
FSE
275
(10.83)
499/635
(19.65/25)
204
(8.03)
235
(9.25)
405/541
(15.94/21.3)
11
(0.43)
300
(11.81)
0
(0)
0
(0)
4 × M8
FSF
350
(13.78)
634/934
(24.96/36.77)
316
(12.44)
300
(11.81)
598/899
(23.54/35.39)
11
(0.43)
350
(13.78)
0
(0)
0
(0)
4 × M8
Drill pattern
Drill pattern
c + Control Unit
c + Control Unit +
IOP/BOP-2
G_D011_EN_00448
c
a
b
FSC - FSF
d
e
f
FSGX
f
e
d
d
1)
Increased depth:
• When the CU230P-2 Control Unit is plugged on, the depth increases by
-
58 mm
(2.28 in)
for frame size FSC
-
49 mm
(1.93 in)
for frame sizes FSD to FSF
• When the CU240B-2 or CU240E-2 Control Unit is plugged on, the depth
increases by
-
40 mm
(1.57 in)
for frame size FSC
-
31 mm
(1.22)
for frame sizes FSD to FSF
• When the CU250S-2 Control Unit is plugged in, the depth increases by
-
61 mm
(2.4 in)
for frame size FSC
-
52 mm
(2.05 in)
for frame sizes FSD to FSF
• When the IOP is plugged on, the depth increases by a further 22 mm
(0.87 in)
• When the BOP-2 is plugged on, the depth increases by a further 12 mm
(0.47 in)
• With the PM240 Power Module, frame size FSGX, the depth does not
increase when devices are plugged on.
2)
Up to 40 °C (104 °F) without any lateral clearance.
© Siemens AG 2016