SIEMENS
6/22
Siemens D 31 N · March 2016
6
SINAMICS G110M distributed inverters
0.37 kW to 4 kW (0.5 hp to 5 hp)
PM240M Power Modules
■
Characteristic curves
Derating data
Ambient temperature
Permissible output current as a function of ambient temperature for
PM240M Power Modules, frame sizes FSA and FSB
Note:
The operating temperature ranges of the Control Units must be
taken into account. The temperature ranges are specified in the
technical specifications under Control Units.
1)
The permissible motor cable length also depends on the cable type
and the selected pulse frequency.
Installation altitude
Permissible output current as a function of installation altitude for
PM240M Power Modules, frame sizes FSA and FSB
Permissible input voltage as a function of installation altitude for PM240M
Power Modules, frame sizes FSA and FSB
Motor frequency
Permissible output current as a function of motor frequency for PM240M
Power Modules, frame sizes FSA and FSB
Rated power at
400 V 3 AC
Rated output current in A
for a pulse frequency of
(derating as a function of the pulse frequency
1)
)
kW
hp
4 kHz
6 kHz
8 kHz
10 kHz
12 kHz
14 kHz
16 kHz
0.37
0.5
1.3
1.3
1.11
0.91
0.78
0.65
0.59
0.75
1
2.2
1.9
1.5
1.3
1.1
1
0.9
1.1
1.5
3.1
2.6
2.2
1.9
1.6
1.4
1.2
1.5
2
4.1
3.5
2.9
2.5
2.1
1.8
1.6
2.2
3
5.6
4.8
3.9
3.4
2.8
2.5
2.2
3
4
7.3
6.2
5.1
4.4
3.7
3.3
2.9
4
5
8.8
7.5
6.2
5.3
4.4
4
3.5
0
20
30
10
40
-10
50 °C
60
75
%
50
25
100
55
55
G_D011_EN_00124
Ambient temperature
Permissible
output current
(32)
(68)
(86)
(50)
(104)
(14)
(122)(°F)
(140)
(131)
80
100
%
0
1000
2000
3000
4000
m
70
90
60
G_D011_EN_00104
Installation altitude above sea level
Permissible
output current
(3281)
(6562)
(9843)
(ft)
(13124)
80
100
%
0
1000
2000
3000
4000
m
77
70
90
60
G_D011_EN_00105
Installation altitude above sea level
Permissible
input voltage
(3281)
(6562)
(9843)
(ft)
(13124)
G_D011_EN_00473
Motor frequency
Permissible
output current
90
70
Hz
10
20
30
40
50
%
100
80
© Siemens AG 2016