SINAMICS G120 standard inverters
0.37 kW to 250 kW (0.5 hp to 400 hp)
SINAMICS G120 standard inverters
5
■
Design
PM230 and PM240-2 Power Modules
Data based on a duty cycle with low overload (LO).
Data based on duty cycle with high overload (HO),
see section Power Modules.
Rated power
1)
Rated output current
I
rated
2)
PM230
Power Module
Degree of protection IP20
3)
The following Control Units
are supported: CU230P-2 ...,
CU240B-2 ..., CU240E-2 ...
PM240-2
Power Modules
Degree of protection IP20
All CUs pluggable
kW
hp
A
Article No.
Article No.
200 ... 240 V 1 AC/3 AC
0.55
0.75
3.2
–
6SL3210-1PB13-0
■
L0
0.75
1
4.2
–
6SL321
■
1 pb13-8
■
L0
1.1
1.5
6
–
6SL3210-1PB15-5
■
L0
1.5
2
7.4
–
6SL3210-1PB17-4
■
L0
2.2
3
10.4
–
6SL321
■
-1PB21-0
■
L0
3
4
13.6
–
6SL3210-1PB21-4
■
L0
4
5
17.5
–
6SL321
■
-1PB21-8
■
L0
200 ... 240 V 3 AC
5.5
7.5
22
–
6SL3210-1PC22-2
■
L0
7.5
10
28
–
6SL3210-1PC22-8
■
L0
11
15
42
–
6SL3210-1PC24-2UL0
15
20
54
–
6SL3210-1PC25-4UL0
18.5
25
68
–
6SL3210-1PC26-8UL0
22
30
80
–
6SL3210-1PC28-0UL0
30
40
104
–
6SL3210-1PC31-1UL0
37
50
130
–
6SL3210-1PC31-3UL0
45
60
154
–
6SL3210-1PC31-6UL0
55
75
178
–
6SL3210-1PC31-8UL0
380 ... 480 V 3 AC
0.37
4)
0.5
1.3
6SL3210-1NE11-3
■
L1
–
4)
0.55
0.75
1.7
6SL3210-1NE11-7
■
L1
6SL3210-1PE11-8
■
L1
0.75
1
2.2
6 sl3210-1ne12-2
■
L1
6SL3210-1PE12-3
■
L1
1.1
1.5
3.1
6SL3210-1NE13-1
■
L1
6SL3210-1PE13-2
■
L1
1.5
2
4.1
6SL3210-1NE14-1
■
L1
6SL3210-1PE14-3
■
L1
2.2
3
5.9
6SL3210-1NE15-8
■
L1
6SL3210-1PE16-1
■
L1
3
4
7.7
6SL321
■
-1NE17-7
■
L1
6SL321
■
-1PE18-0
■
L1
4
5
10.2
6SL3210-1NE21-0
■
L1
6SL3210-1PE21-1
■
L0
Heat sink variant
↑
↑
Standard
0
0
Push-through
1
1
Integrated line filter
↑
↑
Without
(系统)
U
U
Class A
(for TN systems)
A
A
1)
Rated power based on the rated output current
I
rated
. The rated output
当前的
I
rated
is based on the duty cycle for low overload (LO). Low over-
load (LO) generally applies for applications with low dynamic response
(连续操作),quadratic torque characteristic with low break
loose torque and low speed accuracy. Examples: Centrifugal pumps,
radial/axial fans, rotary piston fans, radial compressors, vacuum pumps,
chain conveyors, agitators. High Overload (HO) generally applies for appli-
cations with increased dynamic response (cyclic operation) and constant
torque characteristics with high break loose torque. Examples: Gear
pumps, eccentric worm pumps, mills, mixers, crushers, lifting/lowering
gear, centrifuges.
2)
The rated output current
I
rated
is based on the duty cycle for low overload
(LO). These current values are applicable for 200 V, 400 V or 690 V.
3)
PM230 Power Modules with integrated filter class A or class B, degree of
protection IP55/UL Type 12, 0.37 kW to 90 kW (0.5 to 125 hp) are integral
components of the SINAMICS G120P for pumps, fans and compressors.
The CU230P-2 is the Control Unit for SINAMICS G120P and
SINAMICS G120P Cabinet for pumps, fans and compressors.
More information can be found in Catalog D 35
.
4)
The PM240-2 Power Module with Article No. 6SL3210-1PE11-8. L1
corresponds to 0.37 kW (0.5 hp) with duty cycle HO.
© Siemens AG 2016