SIEMENS
5/74
Siemens D 31 N · March 2016
SINAMICS G120 standard inverters
0.37 kW to 250 kW (0.5 hp to 400 hp)
Power Modules
5
■
Technical specifications
Line voltage 380 ... 480 V 3 AC
PM250 Power Modules
Without integrated line filter
6SL3225-
0BE33-0UA0
6SL3225-
0BE33-7UA0
6SL3225-
0BE34-5UA0
6SL3225-
0BE35-5UA0
6SL3225-
0BE37-5UA0
With integrated line filter
6SL3225-
0BE33-0AA0
6SL3225-
0BE33-7AA0
6SL3225-
0BE34-5AA0
6SL3225-
0BE35-5AA0
6SL3225-
0BE37-5AA0
Output current
at 50 Hz 400 V 3 AC
• Rated current
I
rated
1)
A
75
90
110
145
178
• Base-load current
I
L
1)
A
75
90
110
145
178
• Base-load current
I
H
2)
A
60
75
90
110
145
• Maximum current
I
max
A
120
150
180
220
290
Rated power
• Based on
I
L
kW (hp)
37 (50)
45 (60)
55 (75)
75 (100)
90 (125)
• Based on
I
H
kW (hp)
30 (40)
37 (50)
45 (60)
55 (75)
75 (100)
Rated pulse frequency
kHz
4
4
4
4
4
Efficiency
η
>0.97
>0.97
>0.97
>0.97
>0.97
Power loss
3)
At rated current
kW
1.01
1.217
1.605
2.234
2.638
Cooling air requirement
m
3
/s (ft
3
/s)
0.022 (0.8)
0.039 (1.4)
0.094 (3.3)
0.094 (3.3)
0.117 (4.1)
Sound pressure level
L
pA
(1 m)
dB
<60
<62
<60
<60
<65
24 V DC power supply
for Control Unit
A
1
1
1
1
1
Input current
4)
• Rated current
A
70
84
102
135
166
• Based on
I
H
A
56
70
84
102
135
Line supply connection
U1/L1, V1/L2, W1/L3
M6 screw studs
M6 screw studs
M8 screw studs
M8 screw studs
M8 screw studs
• Conductor cross-section, max.
mm
2
10 ... 50
10 ... 50
25 ... 120
25 ... 120
25 ... 120
Motor connection
U2, V2, W2
M6 screw studs
M6 screw studs
M8 screw studs
M8 screw studs
M8 screw studs
• Conductor cross-section, max.
mm
2
10 ... 50
10 ... 50
25 ... 120
25 ... 120
25 ... 120
PE connection
On housing with
M6 screw
On housing with
M6 screw
On housing with
M8 screw
On housing with
M8 screw
On housing with
M8 screw
Motor cable length
5)
, max.
• Shielded
m (ft)
50 (164)
50 (164)
50 (164)
50 (164)
50 (164)
• Unshielded
m (ft)
100 (328)
100 (328)
100 (328)
100 (328)
100 (328)
Degree of protection
IP20
IP20
IP20
IP20
IP20
Dimensions
• Width
mm (in)
275 (10.83)
275 (10.83)
350 (13.78)
350 (13.78)
350 (13.78)
• Height
-
Without integrated line filter
mm (in)
499 (19.65)
499 (19.65)
634 (24.96)
634 (24.96)
634 (24.96)
-
With integrated line filter
mm (in)
635 (25.0)
635 (25.0)
934 (36.77)
934 (36.77)
934 (36.77)
• Depth
-
Without operator panel
mm (in)
204 (8.03)
204 (8.03)
316 (12.44)
316 (12.44)
316 (12.44)
-
With operator panel, max.
mm (in)
278 (10.94)
278 (10.94)
390 (15.35)
390 (15.35)
390 (15.35)
Frame size
FSE
FSE
FSF
FSF
FSF
Weight, approx.
• Without integrated line filter
kg (lb)
14 (30.9)
14 (30.9)
35 (77.2)
35 (77.2)
35 (77.2)
• With integrated line filter
kg (lb)
21 (46.3)
21 (46.3)
51 (112.5)
51 (112.5)
51 (112.5)
1)
The rated output current
I
rated
and the base-load current
I
L
are based on
the duty cycle for low overload (LO).
2)
The base-load current
I
H
is based on the duty cycle for high overload
(HO).
3)
Typical values. You can find additional information on the Internet at
4)
The input current depends on the motor load and line impedance and
applies for a line impedance corresponding to
u
K
= 1 %. The rated input
currents apply for a load at rated power (based on
I
rated
) – these current
values are specified on the rating plate.
5)
Max. motor cable length 25 m (82 ft) (shielded) for PM250 Power Modules
with integrated line filter to maintain the limit values of EN 61800-3
Category C2.
© Siemens AG 2016