SIEMENS
5/73
Siemens D 31 N · March 2016
SINAMICS G120 standard inverters
0.37 kW to 250 kW (0.5 hp to 400 hp)
Power Modules
5
■
Technical specifications
Line voltage 380 ... 480 V 3 AC
PM250 Power Modules
Without integrated line filter
6SL3225-0BE31-5UA0
6SL3225-0BE31-8UA0
6SL3225-0BE32-2UA0
With integrated line filter
6SL3225-0BE31-5AA0
6SL3225-0BE31-8AA0
6SL3225-0BE32-2AA0
Output current
at 50 Hz 400 V 3 AC
• Rated current
I
rated
1)
A
38
45
60
• Base-load current
I
L
1)
A
38
45
60
• Base-load current
I
H
2)
A
32
38
45
• Maximum current
I
max
A
64
76
90
Rated power
•基于
I
L
kW (hp)
18.5 (25)
22 (30)
30 (40)
•基于
I
H
kW (hp)
15 (20)
18.5 (25)
22 (30)
Rated pulse frequency
kHz
4
4
4
Efficiency
η
>0.97
>0.97
>0.97
Power loss
3)
At rated current
kW
0.576
0.693
0.918
Cooling air requirement
m
3
/s (ft
3
/s)
0.022 (0.8)
0.022 (0.8)
0.039 (1.4)
声压勒vel
L
pA
(1 m)
dB
<60
<60
<61
24 V DC power supply
for Control Unit
A
1
1
1
Input current
4)
• Rated current
A
36
42
56
•基于
I
H
A
30
36
42
Line supply connection
U1/L1, V1/L2, W1/L3
M6 screw stud
M6 screw stud
M6 screw stud
• Conductor cross-section
mm
2
10 ... 35
10 ... 35
10 ... 35
Motor connection
U2, V2, W2
M6 screw stud
M6 screw stud
M6 screw stud
• Conductor cross-section
mm
2
10 ... 35
10 ... 35
10 ... 35
PE connection
On housing with M6 screw
On housing with M6 screw
On housing with M6 screw
Motor cable length
5)
, max.
• Shielded
m (ft)
50 (164)
50 (164)
50 (164)
• Unshielded
m (ft)
100 (328)
100 (328)
100 (328)
Degree of protection
IP20
IP20
IP20
Dimensions
• Width
mm (in)
275 (10.83)
275 (10.83)
275 (10.83)
• Height
-
Without integrated line filter
mm (in)
419 (16.50)
419 (16.50)
419 (16.50)
-
With integrated line filter
mm (in)
512 (20.16)
512 (20.16)
512 (20.16)
• Depth
-
Without operator panel
mm (in)
204 (8.03)
204 (8.03)
204 (8.03)
-
With operator panel, max.
mm (in)
278 (10.94)
278 (10.94)
278 (10.94)
Frame size
FSD
FSD
FSD
Weight, approx.
• Without integrated line filter
kg (lb)
13 (28.7)
13 (28.7)
13 (28.7)
• With integrated line filter
kg (lb)
15 (33.1)
15 (33.1)
16 (35.3)
1)
The rated output current
I
rated
and the base-load current
I
L
are based on
the duty cycle for low overload (LO).
2)
The base-load current
I
H
is based on the duty cycle for high overload
(HO).
3)
Typical values. You can find additional information on the Internet at
4)
The input current depends on the motor load and line impedance and
applies for a line impedance corresponding to
u
K
= 1 %. The rated input
currents apply for a load at rated power (based on
I
rated
) – these current
values are specified on the rating plate.
5)
Max. motor cable length 25 m (82 ft) (shielded) for PM250 Power Modules
with integrated line filter to maintain the limit values of EN 61800-3
Category C2.
© Siemens AG 2016