SIEMENS
5/62
Siemens D 31 N · March 2016
SINAMICS G120 standard inverters
0.37 kW to 250 kW (0.5 hp to 400 hp)
Power Modules
5
■
Technical specifications
Line voltage 200 ... 240 V 3 AC
PM240-2 Power Modules standard variant
Without integrated line filter
6SL3210-
1PC28-0UL0
6SL3210-
1PC31-1UL0
6SL3210-
1PC31-3UL0
6SL3210-
1PC31-6UL0
6SL3210-
1PC31-8UL0
With integrated line filter class A
–
–
–
–
–
Output current
at 50 Hz 230 V 3 AC
• Rated current
I
rated
1)
A
80
104
130
154
178
• Base-load current
I
L
1)
A
80
104
130
154
178
• Base-load current
I
H
2)
A
68
80
104
130
154
• Maximum current
I
max
A
136
160
208
260
308
Rated power
• Based on
I
L
kW (hp)
22 (30)
30 (40)
37 (50)
45 (60)
55 (75)
• Based on
I
H
kW (hp)
18.5 (25)
22 (30)
30 (40)
37 (50)
45 (60)
Rated pulse frequency
kHz
4
4
4
4
4
Efficiency
η
>97
>97
>97
>97
>97
Power loss
3)
At rated current
kW
0.85
1.2
1.3
1.63
1.98
Cooling air requirement
m
3
/s (ft
3
/s)
0.083 (2.9)
0.083 (2.9)
0.153 (5.4)
0.153 (5.4)
0.153 (5.4)
声压级
L
pA
(1 m)
dB
44... 62
4)
44... 62
4)
56 ... 68
4)
56 ... 68
4)
56 ... 68
4)
24 V DC power supply
for Control Unit
A
1
1
1
1
1
Input current
5)
• Rated current
A
76
98
126
149
172
• Based on
I
H
A
71
83
110
138
164
Line supply connection
U1/L1, V1/L2, W1/L3
Screw terminals
Screw terminals
M10 screw stud
M10 screw stud
M10 screw stud
• Conductor cross-section
mm
2
25 ... 70
25 ... 70
35 ... 2 × 120
35 ... 2 × 120
35 ... 2 × 120
Motor connection
U2, V2, W2
Screw terminals
Screw terminals
M10 screw stud
M10 screw stud
M10 screw stud
• Conductor cross-section
mm
2
25 ... 70
25 ... 70
35 ... 2 × 120
35 ... 2 × 120
35 ... 2 × 120
PE connection
Screw terminals
Screw terminals
M10 screw stud
M10 screw stud
M10 screw stud
Motor cable length, max.
• Shielded
m (ft)
200 (656)
200 (656)
300 (984)
300 (984)
300 (984)
• Unshielded
m (ft)
300 (984)
300 (984)
450 (1476)
450 (1476)
450 (1476)
Degree of protection
IP20
IP20
IP20
IP20
IP20
Dimensions
• Width
mm (in)
275 (10.83)
275 (10.83)
305 (12.01)
305 (12.01)
305 (12.01)
• Height
mm (in)
551 (21.69)
551 (21.69)
708 (27.87)
708 (27.87)
708 (27.87)
• Depth
-
Without operator panel
mm (in)
237 (9.33)
237 (9.33)
357 (14.06)
357 (14.06)
357 (14.06)
-
With operator panel, max.
mm (in)
278 (10.94)
278 (10.94)
398 (15.67)
398 (15.67)
398 (15.67)
Frame size
FSE
FSE
FSF
FSF
FSF
Weight, approx.
• Without integrated line filter
kg (lb)
26 (57.3)
26 (57.3)
57 (126)
57 (126)
57 (126)
• With integrated line filter
kg (lb)
–
–
–
–
–
1)
The rated output current
I
rated
and the base-load current
I
L
are based on
the duty cycle for low overload (LO).
2)
The base-load current
I
H
is based on the duty cycle for high overload
(HO).
3)
Typical values. You can find additional information on the Internet at
4)
Values dependent on ambient temperature and utilization.
5)
The input current depends on the motor load and line impedance. The
input currents apply for a load at rated power (based on
I
rated
) for a line
impedance corresponding to
u
K
= 1 %. The current values are specified
on the rating plate of the Power Module.
© Siemens AG 2016