关于操作高压电机的一般注意事项
如果通过驱动,高压电机可以产生电压
the load as a result of the inherent plant or system principle. The
该电压的幅度基本上取决于速度和
the type of excitation of the high-voltage motor. The following
must be noted in order to ensure that the converter power unit
safely and reliably operates while the high-voltage motor is
rotating:
•
For permanent-magnet synchronous motors, options
L49
(转换器输出处的禁用接地开关)和
L52
(转换器输出处的断路器)必须
是选择。
•
用于感应电机和单独激发同步
电机,如果电机由负载驱动,则选项
L49
和
L51 / L52
(取决于特定的申请)应该
是
选择。
Operation of Siemens high-voltage motors
A sine-wave filter is not required between the Siemens high-
电压电机H-Compact,H-Compact Plus,H-Modyn和
special motors for e.g. marine, rolling mill and high-speed
应用程序和SINAMICS GM150和SINAMICS SM150
转换器。驱动器的可靠运行确保了
以下措施:
•
The MICALASTIC VPI insulation system is optimally suited for
转换器操作中发生的电压应力。
•
从中喂养时的高压电机的保护概念
converters involves two insulating bearings to avoid damag-
ing bearing currents. Further, shaft grounding is absolutely
必要的使电动机可以在电动机上建立电压
轴相对于地面。轴是接地的
using a rotary pulse encoder with integrated grounding track
在非驱动端或使用单独的接地刷
the motor drive end. In the first case, an insulated coupling
must be used. This is because as a result of the shaft ground-
ing at the non-drive end, circulating currents can flow through
驱动的负荷。在第二种情况下,旋转脉冲编码器
必须安装在非驱动端,使其绝缘;
不需要绝缘耦合
(见图)
。
Minimum motor rated frequency:
•
SINAMICS GM150在IGBT版本和
SINAMICS SM150 in IGBT version:
20 Hz.
•
Sinamics Gm150在IGCT版本中
SINAMICS SM150 in IGCT version:
- 8.5 Hz,输出电压为3.3 kV
-5.。0 Hz for a reduced voltage of 3.15 kV
笔记:
请联系您的区域西门子销售伙伴
不同数据的情况。
笔记
:
For motors with rated frequency of less than 8.5 Hz, a reduced
voltage of 3.15 kV should always be selected.
轴接地在非驱动端
Shaft grounding at the drive end
Insulated
耦合
加载
Insulated
耦合
Shaft grounding
旋转脉冲编码器
发动机
绝缘轴承
加载
Shaft grounding
旋转脉冲编码器
发动机
发动机
G_D012_EN_00048
加载
耦合
Shaft grounding
旋转脉冲编码器
发动机
绝缘轴承
加载
耦合
Shaft grounding
旋转脉冲编码器