Engineering information
SINAMICS GM150, SINAMICS SM150
Overview of interfaces
9/6
Siemens D 12 · 2012
9
■
Configuration
Terminal strip on TM15
(SINAMICS GM150: =.HC-A31, SINAMICS SM150: =.HC-A11)
Terminal
Type
Preassignment
X520:
2
DI
/DO0
Bidirectional
digital inputs
and outputs
1)
Free
3
DI
/DO1
ON / OFF1
4
DI
/DO2
OUT2
5
DI
/DO3
OUT3
6
DI
/DO4
Acknowledgement
7
DI
/DO5
Free
8
DI
/DO6
Inverter enable
9
DI
/DO7
Control bit 1
(increase setpoint)
X521:
2
DI
/DO8
Bidirectional
digital inputs
and outputs
1)
Control bit 2 command
(decrease setpoint)
3
DI
/DO9
Control bit 3 command
(select fixed setpoint bit 0)
4
DI
/DO10
Control bit 4 command
(select fixed setpoint bit 1)
5
DI
/DO11
Select command data set
bit 0
6
DI
/DO12
Switchover of direction of
rotation
7
DI/DO13
Ready to start message
8
DI/DO14
Ready to run message
9
DI/DO15
Operating message
X522:
2
DI/DO16
Bidirectional
digital inputs
and outputs
1)
Converter fault message
3
DI/DO17
Converter warning message
4
DI/DO18
Local/remote operating
status message
5
DI/DO19
Drive rotates to the right
(clockwise)
6
DI
/DO20
Free
7
DI
/DO21
Free
8
DI
/DO22
Free
9
DI
/DO23
Free
=.EF–X21:
8
P24
The jumper must be removed
according to the control
mode (non-isolated/isolated).
=.EF–X22:
8
M
The jumper must be removed
according to the control
mode (non-isolated/isolated).
Terminal strip on isolation amplifier
Terminal
Preassignment
Comment
=.LC–A21:
1
Main speed setpoint
(4 ... 20 mA)
Signal level adjustable
(0 ... 10 V; 0 ... 20 mA;
4 ... 20 mA)
2
=.LC–A22:
1
Supplementary speed
setpoint (4 ... 20 mA)
Signal level adjustable
(0 ... 10 V; 0 ... 20 mA;
4 ... 20 mA)
2
=.LC–A41:
1
Main speed actual
value (4 ... 20 mA)
Signal level adjustable
(0 ... 10 V; 0 ... 20 mA;
4 ... 20 mA)
2
=.LC–A42:
1
Supplementary speed
actual value
(4 ... 20 mA)
Signal level adjustable
(0 ... 10 V; 0 ... 20 mA;
4 ... 20 mA)
2
Temperature monitoring with Pt100 evaluation unit
Terminal
Type
Comment
=.LD–A11:
1T1 to 1T3
Pt100
Sensor 1
2T1 to 2T3
Pt100
Sensor 2
3T1 to 3T3
Pt100
Sensor 3
The sensors can be connected to the Pt100 evaluation unit using either
a two-wire or three-wire system. In the two-wire system, inputs xT1 and
xT2 must be assigned and terminals xT2 and xT3 must be jumpered.
The limit values for warning and shutdown must be set centrally for all
three sensors.
The output relays are integrated into the internal fault and shutdown
sequence of the converter. The signals can also be picked up in the
plant side by means of two spare fault signaling relays.
Incorporating an external safety shutdown, SINAMICS GM150
Terminal
Type
Comment
=.EF–X21:
18
External safety
shutdown
Jumper = EF-X21:18-19
should be removed when
incorporating the external
safety shutdown.
19
=.EF–X22:
18
Reference ground
If the power supply is
externally provided, then
jumper = EF-X22:18-19
must be removed and the
reference ground of the
external supply must be
connected with = EF-X22:19.
19
1)
The digital inputs/outputs can be parameterized individually as inputs or
outputs (electrical isolation in three groups of eight channels each). The
preassignment as an input or output is identified by underlining
.