SIEMENS
Description of options
SINAMICS GM150, SINAMICS SM150
Description of options
6/18
Siemens D 12 · 2012
6
■
Options
Terminal connection overview for IGCT version
Terminal strip at TM31 (=.HD–A11)
Terminal
Type
Preassign-
ment
Comment
X540:
1-8
P24
24 V DC supply for
inputs DI0 to DI7
–
–
X520:
1
DI0
Digital input
electrically isolated
via optocoupler
–
Pre-assigned
for options
L91 to L96
2
DI1
–
3
DI2
–
Pre-assigned
for options
L92 to L96
4
DI3
–
5
M1
Reference ground
for digital inputs
DI0 to DI3
–
–
6
M
Reference ground
for P24, auxiliary
voltage for digital
inputs
–
–
X530:
1
DI4
Digital input
electrically isolated
via optocoupler
–
Pre-assigned
for options
L90 to L92
2
DI5
–
3
DI6
–
Pre-assigned
for options
L80 to L82
4
DI7
–
5
M2
Reference ground
for digital inputs
DI4 to DI7
–
–
6
M
Reference ground
for P24, auxiliary
voltage for digital
inputs
–
–
X541:
1
P24
24 V DC supply
for inputs/outputs
DI/O8 to DI/DO11
–
–
2
DI/DO8
Digital inputs/
digital outputs
non-isolated
–
Pre-assigned
for options
L81 and L82
3
DI/DO9
–
4
DI/DO10
–
Pre-assigned
for option L82
5
DI/DO11
–
6
M
Reference ground
for P24, ground
of digital inputs/
digital outputs
–
–
Terminal strip at TM31 (=.HD–A11)
Terminal
Type
Preassign-
ment
Comment
X521:
1
AI0+
Analog inputs set
up as differential
inputs for the
following ranges:
-10 ... +10 V
+4 ... +20 mA
0 ... +20 mA
-20 ... +20 mA
The voltage input/
current input is
selected with a
switch
–
–
2
AI0-
3
AI1+
–
–
4
AI1-
5
P10
Auxiliary voltage
± 10 V (10 mA) to
connect a poten-
tiometer to enter a
setpoint via an
analog input
–
–
6
M
–
–
7
N10
–
–
8
M
–
–
X522:
1
AO 0V+
Analog outputs
for the following
ranges:
-10 ... +10 V
+4 ... +20 mA
0 ... +20 mA
-20 ... +20 mA
–
–
2
AO 0V-
Pre-assigned
for options
L93 to L96
3
AO0C+
–
4
AO 1V+
–
–
5
AO 1V-
Pre-assigned
for options
L93 to L96
6
AO 1C+
–
7
KTY+
Temperature sensor
KTY84 0 ... 200 °C
or PTC
(
R
cold
< 1.5 k
Ω
)
–
The sensor
type must be
parameter-
ized
8
KTY-
–
X542:
1
DO 0.NC
Relay output for
changeover contact
Max. switching
voltage:
250 V AC, 30 V DC
Max. switching
power at 250 V AC:
2000 VA
Max. switching
power at 30 V DC:
240 W
–
NC contact
2
DO 0.COM
–
Basic
3
DO 0.NO
–
NO contact
4
DO 1.NC
Relay output for
changeover contact
Max. switching
voltage: 250 V AC,
30 V DC
Max. switching
power at 250 V AC:
2000 VA
Max. switching
power at 30 V DC:
240 W
–
NC contact
5
做1. com
–
Basic
6
DO 1.NO
–
NO contact
© Siemens AG 2012