SIEMENS
Description of options
SINAMICS GM150, SINAMICS SM150
Description of options
6/16
Siemens D 12 · 2012
6
■
Options
G61
Additional TM31 Terminal Module
One TM31 Terminal Module and two TM15 Terminal Modules for
integrating warning and fault messages and drive signals and
for communicating with a higher control level are already in-
cluded in the standard version of the converter. If the number of
signals to be monitored is not sufficient, the interface can also be
extended by an additional Terminal Module. Additional digital
inputs and outputs and two analog inputs and outputs are avail-
able with the TM31.
The TM31 Terminal Module has:
•
8 digital inputs
•
4 bidirectional digital inputs and outputs
•
2 relay outputs with changeover contact
•
2模拟输入
•
2 analog outputs
•
1 temperature sensor (KTY84-130 or PTC)
The following table shows an overview of the exclusions, which
必须是公司nsidered when selecting options
G61
or
G62
.
Note:
For isolated analog inputs/outputs, options
E86
or
E87
are
available.
G61
G62
E86
E87
L80
to L93,
L95
L94,
L96
G61
✓
✓
✓
–
–
G62
✓
–
–
✓
–
E86
✓
–
✓
✓
–
E87
✓
–
✓
✓
✓
L80 bis L93, L95
–
✓
✓
✓
✓
L94, L96
–
–
–
✓
✓
✓
Options can be combined
–
Options are mutually exclusive
TM31 Terminal Module
Digital inputs
• Voltage
-3 ... +30 V
• Low level
(an open digital input is
interpreted as "low")
-3 ... +5 V
• High level
15 ... 30 V
• Current consumption
at 24 V DC, typ.
10 mA
• Signal propagation times of
digital inputs, approx.
- L
→
H
50
µ
s
- H
→
L
100
µ
s
• Conductor cross-section, max.
1.5 mm
2
Digital outputs
(sustained short-circuit strength)
• Voltage
24 V DC
• Load current per digital output,
max.
100 mA
• Total current of digital outputs,
max.
400 mA
• Conductor cross-section, max.
1.5 mm
2
Analog inputs
(a switch is used to toggle
between voltage and current input)
• As voltage input
-
Voltage range
-10 ... +10 V
-
Internal resistance
R
i
100 k
Ω
• As current input
-
Current range
4 ... 20 mA/-20 ... +20 mA,
0 ... 20 mA
-
Internal resistance
R
i
250
Ω
- Resolution
11 bit + sign
• Conductor cross-section, max.
1.5 mm
2
Analog outputs
(sustained short-circuit strength)
• Voltage range
-10 ... +10 V
• Load current, max.
-3 ... +3 mA
• Current range
4 ... 20 mA, -20 ... +20 mA,
0 ... 20 mA
• Load resistance, max.
500
Ω
for outputs in the range
-20 ... +20 mA
• Resolution
11 bit + sign
• Conductor cross-section, max.
1.5 mm
2
Relay outputs
(changeover contacts)
• Load current, max.
8 A
• Operating voltage, max.
250 V AC, 30 V DC
• Switching power
at 250 V AC, max.
2000 VA (cos
ϕ
= 1)
750 VA (cos
ϕ
= 0.4)
• Switching power
at 30 V DC, max.
240 W (ohmic load)
• Required minimum current
100 mA
• Conductor cross-section, max.
2.5 mm
2
© Siemens AG 2012