SIEMENS
SINAMICS SM150
Medium-Voltage Converter
SINAMICS SM150 in IGCT version
Water cooling
5/21
Siemens D 12 · 2012
5
■
Technical specifications
Note:
For other technical requirements that have to be taken into consideration (surge loads, operation at low frequencies, possibly
necessary derating for parallel circuit configurations) please contact your Siemens sales partner indicating the required specifica-
tions. Additional DC bus configurations are available on request.
SINAMICS SM150 in the IGCT version
Water cooling
6SL3845-
7NN41-8AD0
6SL3845-
7NN41-8AF0
6SL3845-
7NN41-8AG0
6SL3845-
7NN41-8AK0
6SL3845-
7NN43-6AF0
Output voltage 3.3 kV
Type rating
kVA
10000
10000
10000
10000
20000
Shaft output
1)
kW
9600
2)
9600
2)
9600
2)
9600
2)
19200
2)
hp
13000
2)
13000
2)
13000
2)
13000
2)
26000
2)
Rated output current
A
4 × 1750
3 × 1750
4 × 1750
5 × 1750
1 × (2 × 1750)
+2 × 1750
Input voltage
kV
3.3
2×3.3
2×3.3
2×3.3
2×3.3
Rated input current
1)
A
1770
2 × 1770
2 × 1770
2 × 1770
2 × 1770
Power loss
3) 4)
kW
250
250
300
350
300
Efficiency
4)
%
97.5
97.5
97
99
98.4
Typ. current demand
of the auxiliary supply
230 V 1 AC, 50/60 Hz
5)
A
15
15
18
21
18
Max. current demand
of the auxiliary supply
400 V 3 AC, 50/60 Hz
A
22
22
23
24
23
Precharging current
demand,
briefly for approx. 25 s
A
20
40
40
40
40
Raw water flow rate
l/min
1000
1000
1000
1333
1000
Deionized water
requirement, approx.
l
275
275
300
350
300
Sound pressure level
L
pA
(1 m)
dB
78
78
79
79
79
Measuring surface level
L
s
(1 m)
dB
24
24
24
24
24
Cable cross-sections,
line-side, max.
connectable per phase
6) 7)
mm
2
(DIN VDE)
6 × 240
6 × 240
6 × 240
6 × 240
6 × 240
AWG/MCM
(NEC, CEC)
6 × 500 MCM
6 × 500 MCM
6 × 500 MCM
6 × 500 MCM
6 × 500 MCM
Cable cross-sections,
motor-side, max.
connectable per phase
6) 7)
mm
2
(DIN VDE)
6 × 240
6 × 240
6 × 240
6 × 240
6 × 240
AWG/MCM
(NEC, CEC)
6 × 500 MCM
6 × 500 MCM
6 × 500 MCM
6 × 500 MCM
6 × 500 MCM
PE connection,
max. connection cross-
section at the enclosure
with M12 screw
6)
mm
2
(DIN VDE)
2 × 120
2 × 120
2 × 120
2 × 120
2 × 120
AWG/MCM
(NEC, CEC)
2 × 250 MCM
2 × 250 MCM
2 × 250 MCM
2 × 250 MCM
2 × 250 MCM
Degree of protection
IP43
IP43
IP43
IP43
IP43
Dimensions
8)
• Width
mm
13500
13500
15800
18100
15800
• Height
9)
mm
2540
2540
2540
2540
2540
• Depth
mm
1600
1600
1600
1600
1600
Circuit version
(Pages 5/5 to 5/7)
Fig. No.
4
5
6
7
8
Weight
8)
kg
14800
14800
17500
20200
17500
Footnotes see page 5/23.
© Siemens AG 2012