年代IEMENS
年代INAMICS G180
Configuring instructions
Cable cross-sections and connections
5/12
年代iemens D 18.1 · 2014
5
■
Overview
(continued)
Type
rating
Converter
Converter type
Line connection
(standard)
Line connection
with main
switch or circuit breaker
(Options:
年代01
,
年代02
,
年代03
,
年代04
,
年代06
,
年代08
,
年代09
,
年代11
,
年代12
,
年代21
,
年代22
,
年代23
,
年代24
,
年代41
)
Motor connection
年代INAMICS G180
Cable cross-
section
solid/stranded
Fixing
Cable cross-
section
solid/stranded
Fixing
Cable cross-
section
solid/stranded
Fixing
min.
max.
min.
max.
min.
max.
kW
IEC
mm²
IEC
mm²
IEC
mm²
IEC
mm²
IEC
mm²
IEC
mm²
年代INAMICS G180 cabinet units 690 V 12-pulse, air-cooled and liquid-cooled (2 × 400 to 600
1)
/690 V 3 AC IT system, 50 to 60 Hz)
250
6SE01.0-2BH33-2.A7
2T.F-.7601-250
2 × 2.5
2 × 150
1 × M6
1 × 10
2 × 150
1 × 300
2 × 300
1 × M12
315
6SE01.0-2BH33-6.A7
2T.F-.7601-315
2 × 6
2 × 185
1 × M10
1 × 10
2 × 150
1 × 300
2 × 300
1 × M12
400
6SE01.0-2BH34-2.A7
2T.F-.7601-400
2 × 6
2 × 185
1 × M10
1 × 10
2 × 150
1 × 300
2 × 300
1 × M12
500
6SE01.0-2BH35-2.A7
2T.F-.7601-500
2 × 6
2 × 300
1 × M10
3 × 10
6 × 150
3 × 300
6 × 300
3 × M12
560
6SE01.0-2BH35-7.A7
2T.F-.7601-560
2 × 6
2 × 300
1 × M10
4 × 10
8 × 150
4 × 300
8 × 300
4 × M12
630
6SE01.0-2BH36-4.A7
2 t.f .7601 - 630
2 × 6
2 × 300
1 × M10
4 × 10
8 × 150
4 × 300
8 × 300
4 × M12
710
6SE01.0-2BH37-1.A7
2T.F-.7601-710
2 × 6
2 × 300
1 × M10
4 × 10
8 × 150
4 × 300
8 × 300
4 × M12
800
6SE01.0-2BH37-7.A7
2T.F-.7601-800
2 × 6
2 × 300
1 × M10
4 × 10
8 × 150
4 × 300
8 × 300
4 × M12
900
6SE01.0-2BH41-0.A7
2T.F-.7601-909
2 × 6
2 × 300
1 × M10
4 × 10
8 × 150
4 × 300
8 × 300
4 × M12
1000
6SE01.0-2BH41-1.A7
2T.F-.7601-910
2 × 6
2 × 300
1 × M10
4 × 10
8 × 150
4 × 300
8 × 300
4 × M12
1200
6SE01.0-2CH41-2.A7
2T.F-.7602-912
2 × 10
4 × 120
2 × 300
4 × 300
2 × M12
8 × 10
16 × 150
8 × 300
16 × 300
2 × 4 ×
M12
1300
6SE01.0-2CH41-3.A7
2T.F-.7602-913
2 × 10
4 × 120
2 × 300
4 × 300
2 × M12
8 × 10
16 × 150
8 × 300
16 × 300
2 × 4 ×
M12
1500
6SE01.0-2CH41-5.A7
2T.F-.7602-915
2 × 10
4 × 120
2 × 300
4 × 300
2 × M12
8 × 10
16 × 150
8 × 300
16 × 300
2 × 4 ×
M12
1100
6SE01.0-2CH41-7.A7
2T.F-.7602-917
2 × 10
4 × 120
2 × 300
4 × 300
2 × M12
8 × 10
16 × 150
8 × 300
16 × 300
2 × 4 ×
M12
1900
6SE01.0-2CH42-0.A7
2T.F-.7602-919
2 × 10
4 × 120
2 × 300
4 × 300
2 × M12
8 × 10
16 × 150
8 × 300
16 × 300
2 × 4 ×
M12
2000
6SE01.0-2DH42-2.A7
2T.F-.7603-920
2 × 10
4 × 120
2 × 300
4 × 300
2 × M12
12 × 10
24 × 150
12 × 120
24 × 300
3 × 4 ×
M12
2300
6SE01.0-2DH42-4.A7
2T.F-.7603-923
2 × 10
4 × 120
2 × 300
4 × 300
2 × M12
12 × 10
24 × 150
12 × 120
24 × 300
3 × 4 ×
M12
2600
6SE01.0-2DH42-7.A7
2T.F-.7603-926
2 × 10
4 × 120
2 × 300
4 × 300
2 × M12
12 × 10
24 × 150
12 × 120
24 × 300
3 × 4 ×
M12
2900
6SE01.0-2DH43-0.A7
2T.F-.7603-929
2 × 10
4 × 120
2 × 300
4 × 300
2 × M12
12 × 10
24 × 150
12 × 120
24 × 300
3 × 4 ×
M12
3100
6SE01.0-2EH43-2.A7
2T.F-.7604-931
2)
2)
2)
16 × 10
32 × 150
16 × 120
32 × 300
4 × 4 ×
M12
3500
6SE01.0-2EH43-6.A7
2T.F-.7604-935
2)
2)
2)
16 × 10
32 × 150
16 × 120
32 × 300
4 × 4 ×
M12
3900
6SE01.0-2EH44-0.A7
2T.F-.7604-939
2)
2)
2)
16 × 10
32 × 150
16 × 120
32 × 300
4 × 4 ×
M12
1)
With an NRTL unit ("U" in 14th position of article number), the voltage range
ends at max. 600 V, otherwise at 690 V.
2)
On request.
© Siemens AG 2014