SIEMENS
SINAMICS G180
Configuring instructions
Cable cross-sections and connections
5/11
Siemens D 18.1 · 2014
5
■
Overview
(continued)
Type
rating
Converter
Converter type
Line connection
(standard)
Line connection
with main
switch or circuit breaker
(Options:
S01
,
S02
,
S03
,
S04
,
S06
,
S08
,
S09
,
S11
,
S12
,
S21
,
S22
,
S23
,
S24
,
S41
)
Motor connection
SINAMICS G180
Cable cross-
section
solid/stranded
Fixing
Cable cross-
section
solid/stranded
Fixing
Cable cross-
section
solid/stranded
Fixing
min.
max.
min.
max.
min.
max.
kW
IEC
mm²
IEC
mm²
IEC
mm²
IEC
mm²
IEC
mm²
IEC
mm²
SINAMICS G180 cabinet units 500 V 12-pulse, air-cooled and liquid-cooled (2 × 230 to 500 V 3 AC IT system, 50 to 60 Hz)
250
6SE01.0-2BD33-7.A7
2T.F-.7501-250
2 × 6
2 × 185
1 × M10
1 × 10
2 × 150
1 × 300
2 × 300
1 × M12
315
6 se01.0 - 2 - bd34 - 6. - a7
2T.F-.7501-315
2 × 6
2 × 185
1 × M10
1 × 10
2 × 150
1 × 300
2 × 300
1 × M12
400
6SE01.0-2BD36-3.A7
2T.F-.7501-400
2 × 6
2 × 300
1 × M10
1 × 10
2 × 150
1 × 300
2 × 300
1 × M12
500
6SE01.0-2BD37-3.A7
2T.F-.7501-500
2 × 6
2 × 300
1 × M10
3 × 10
6 × 150
3 × 300
6 × 300
3 × M12
560
6 se01.0 - 2 - bd38 - 2. - a7
2T.F-.7501-560
2 × 6
2 × 300
1 × M10
4 × 10
8 × 150
4 × 300
8 × 300
4 × M12
630
6SE01.0-2BD38-8.A7
2T.F-.7501-630
2 × 6
2 × 300
1 × M10
4 × 10
8 × 150
4 × 300
8 × 300
4 × M12
710
6SE01.0-2BD41-0.A7
2T.F-.7501-710
2 × 6
2 × 300
1 × M10
4 × 10
8 × 150
4 × 300
8 × 300
4 × M12
800
6SE01.0-2BD41-1.A7
2T.F-.7501-800
2 × 6
2 × 300
1 × M10
4 × 10
8 × 150
4 × 300
8 × 300
4 × M12
SINAMICS G180 cabinet units 690 V 6-pulse, air-cooled and liquid-cooled (230 to 600
1)
/690 V 3 AC TN/TT or IT system, 50 to 60 Hz)
250
6SE01.0-1B.33-2.A7
2T.A-.7601-250
2 × 10
2 × 300
1 × M12
1 × 2.5
2 × 95
1 × 150
2 × 150
1 × M8
1 × 10
2 × 150
1 × 300
2 × 300
1 × M12
315
6SE01.0-1B.33-6.A7
2T.A-.7601-315
2 × 10
2 × 300
1 × M12
1 × 2.5
2 × 95
1 × 150
2 × 150
1 × M8
1 × 10
2 × 150
1 × 300
2 × 300
1 × M12
400
6SE01.0-1B.34-2.A7
2T.A-.7601-400
2 × 10
2 × 300
1 × M12
2 × 10
2 × 300
1 × M12
1 × 10
2 × 150
1 × 300
2 × 300
1 × M12
500
6SE01.0-1B.35-2.A7
2T.A-.7601-500
2 × 10
2 × 300
1 × M12
2 × 6
2 × 300
1 × M10
3 × 10
6 × 150
3 × 300
6 × 300
3 × M12
560
6SE01.0-1B.35-7.A7
2T.A-.7601-560
4 × 10
4 × 300
2 × M12
2 × 10
4 × 120
2 × 300
4 × 300
2 × M12
4 × 10
8 × 150
4 × 300
8 × 300
4 × M12
630
6SE01.0-1B.36-4.A7
2T.A-.7601-630
4 × 10
4 × 300
2 × M12
2 × 10
4 × 120
2 × 300
4 × 300
2 × M12
4 × 10
8 × 150
4 × 300
8 × 300
4 × M12
710
6SE01.0-1B.37-1.A7
2T.A-.7601-710
4 × 10
4 × 300
2 × M12
2 × 10
4 × 120
2 × 300
4 × 300
2 × M12
4 × 10
8 × 150
4 × 300
8 × 300
4 × M12
800
6SE01.0-1B.37-7.A7
2 t.a .7601 - 800
4 × 10
4 × 300
2 × M12
2 × 10
4 × 120
2 × 300
4 × 300
2 × M12
4 × 10
8 × 150
4 × 300
8 × 300
4 × M12
900
6SE01.0-1B.41-0.A7
2T.A-.7601-909
4 × 10
4 × 300
2 × M12
2 × 10
4 × 120
2 × 300
4 × 300
2 × M12
4 × 10
8 × 150
4 × 300
8 × 300
4 × M12
1000
6SE01.0-1B.41-1.A7
2T.A-.7601-910
4 × 10
4 × 300
2 × M12
2 × 10
4 × 120
2 × 300
4 × 300
2 × M12
4 × 10
8 × 150
4 × 300
8 × 300
4 × M12
1200
6SE01.0-1C.41-2.A7
2T.A-.7602-912
8 × 10
8 × 300
2 × 2 × M12
2 × 10
4 × 120
2 × 300
4 × 300
2 × M12
8 × 10
16 × 150
8 × 300
16 × 300
2 × 4 ×
M12
1300
6SE01.0-1C.41-3.A7
2T.A-.7602-913
8 × 10
8 × 300
2 × 2 × M12
2 × 10
4 × 120
2 × 300
4 × 300
2 × M12
8 × 10
16 × 150
8 × 300
16 × 300
2 × 4 ×
M12
1500
6SE01.0-1C.41-5.A7
2T.A-.7602-915
8 × 10
8 × 300
2 × 2 × M12
2 × 10
4 × 120
2 × 300
4 × 300
2 × M12
8 × 10
16 × 150
8 × 300
16 × 300
2 × 4 ×
M12
1100
6SE01.0-1C.41-7.A7
2T.A-.7602-917
8 × 10
8 × 300
2 × 2 × M12
2)
2)
2)
8 × 10
16 × 150
8 × 300
16 × 300
2 × 4 ×
M12
1900
6SE01.0-1C.42-0.A7
2T.A-.7602-919
8 × 10
8 × 300
2 × 2 × M12
2)
2)
2)
8 × 10
16 × 150
8 × 300
16 × 300
2 × 4 ×
M12
1)
With an NRTL unit ("U" in 14th position of article number), the voltage range
ends at max. 600 V, otherwise at 690 V.
2)
On request.
© Siemens AG 2014