SIEMENS
SINAMICS G180
Configuring instructions
Cable cross-sections and connections
5/8
Siemens D 18.1 · 2014
5
■
Overview
Type
rating
Converter
Converter type
Line connection
(standard)
Line connection
with main
switch or circuit breaker
(Options:
S01
,
S02
,
S03
,
S04
,
S06
,
S08
,
S09
,
S11
,
S12
,
S21
,
S22
,
S23
,
S24
,
S41
)
Motor connection
SINAMICS G180
Cable cross-
section
solid/stranded
Fixing
Cable cross-
section
solid/stranded
Fixing
Cable cross-
section
solid/stranded
Fixing
min.
max.
min.
max.
min.
max.
kW
IEC
mm²
IEC
mm²
IEC
mm²
IEC
mm²
IEC
mm²
IEC
mm²
SINAMICS G180 compact unit 400 V 6-pulse (230 to 500 V 3 AC TN/TT system, 50 to 60 Hz)
2.2
6SE0100-1AC15-5.A7
2T2A-07400-002
0.2
6
Terminal
1
16
Terminal
0.2
6
Terminal
3
6SE0100-1AC17-0.A7
2T2A-07400-003
0.2
6
Terminal
1
16
Terminal
0.2
6
Terminal
4
6SE0100-1AC21-0.A7
2T2A-07400-004
0.2
6
Terminal
1
16
Terminal
0.2
6
Terminal
5.5
6SE0100-1AC21-3.A7
2T2A-07400-005
0.2
6
Terminal
1
16
Terminal
0.2
6
Terminal
7.5
6SE0100-1AC21-8.A7
2T2A-07400-007
4
16
Terminal
1
16
Terminal
4
16
Terminal
11
6SE0100-1AC22-5.A7
2T2A-07400-011
4
16
Terminal
1
16
Terminal
4
16
Terminal
15
6SE0100-1AC23-7.A7
2T2A-07400-015
0.75
35
Terminal
2.5
35
Terminal
0.75
35
Terminal
22
6SE0100-1AC24-8.A7
2T2A-07400-022
0.75
35
Terminal
2.5
35
Terminal
0.75
35
Terminal
30
6SE0100-1AC25-8.A7
2T2A-07400-030
0.75
35
Terminal
2.5
35
Terminal
0.75
35
Terminal
37
6SE0100-1AC27-8.A7
2T2A-07400-037
2.5
120
1 × M8
2.5
95
Terminal
2.5
120
1 × M8
45
6SE0100-1AC28-8.A7
2T2A-07400-045
2.5
120
1 × M8
2.5
95
Terminal
2.5
120
1 × M8
55
6SE0100-1AC31-1.A7
2T2A-07400-055
2.5
120
1 × M8
2.5
95
Kemme
2.5
120
1 × M8
75
6SE0100-1AC31-5.A7
2T2A-07400-075
2.5
120
1 × M8
2.5
95
Kemme
2.5
120
1 × M8
90
6SE0100-1AC31-8.A7
2T2A-07400-090
2.5
120
1 × M8
2.5
150
Terminal
2.5
120
1 × M8
110
6SE0100-1AC32-1.A7
2T2A-07400-110
2.5
120
1 × M8
2.5
150
Terminal
2.5
120
1 × M8
132
6SE0100-1AC32-5.A7
2T2A-07400-132
2 × 6
2 × 240
1 × M10
2 × 6
2 × 240
1 × M10
160
6SE0100-1AC33-0.A7
2T2A-07400-160
2 × 6
2 × 240
1 × M10
2 × 6
2 × 240
1 × M10
SINAMICS G180 compact unit 500 V 6-pulse (230 to 500 V 3 AC IT system, 50 to 60 Hz)
2.2
6SE0100-1AD14-5.A7
2T2A-07500-002
0.2
6
Terminal
1
16
Terminal
0.2
6
Terminal
3
6SE0100-1AD15-5.A7
2T2A-07500-003
0.2
6
Terminal
1
16
Terminal
0.2
6
Terminal
4
6SE0100-1AD17-0.A7
2T2A-07500-004
0.2
6
Terminal
1
16
Terminal
0.2
6
Terminal
5.5
6SE0100-1AD21-0.A7
2T2A-07500-005
0.2
6
Terminal
1
16
Terminal
0.2
6
Terminal
7.5
6SE0100-1AD21-3.A7
2T2A-07500-007
0.2
6
Terminal
1
16
Terminal
0.2
6
Terminal
11
6SE0100-1AD21-8.A7
2T2A-07500-011
4
16
Terminal
1
16
Terminal
4
16
Terminal
15
6SE0100-1AD22-5.A7
2T2A-07500-015
4
16
Terminal
1
16
Terminal
4
16
Terminal
22
6SE0100-1AD23-7.A7
2T2A-07500-022
0.75
35
Terminal
2.5
35
Terminal
0.75
35
Terminal
30
6SE0100-1AD24-8.A7
2T2A-07500-030
0.75
35
Terminal
2.5
35
Terminal
0.75
35
Terminal
37
6SE0100-1AD25-8.A7
2T2A-07500-037
0.75
35
Terminal
2.5
35
Terminal
0.75
35
Terminal
45
6SE0100-1AD27-8.A7
2T2A-07500-045
2.5
120
1 × M8
2.5
95
Terminal
2.5
120
1 × M8
55
6SE0100-1AD28-8.A7
2T2A-07500-055
2.5
120
1 × M8
2.5
95
Terminal
2.5
120
1 × M8
75
6SE0100-1AD31-1.A7
2T2A-07500-075
2.5
120
1 × M8
2.5
95
Kemme
2.5
120
1 × M8
90
6SE0100-1AD31-5.A7
2T2A-07500-090
2.5
120
1 × M8
2.5
95
Kemme
2.5
120
1 × M8
110
6SE0100-1AD31-8.A7
2T2A-07500-110
2.5
120
1 × M8
2.5
150
Terminal
2.5
120
1 × M8
132
6SE0100-1AD32-1.A7
2T2A-07500-132
2.5
120
1 × M8
2.5
150
Terminal
2.5
120
1 × M8
160
6SE0100-1AD32-5.A7
2T2A-07500-160
2 × 6
2 × 240
1 × M10
2 × 6
2 × 240
1 × M10
200
6SE0100-1AD33-0.A7
2T2A-07500-200
2 × 6
2 × 240
1 × M10
2 × 6
2 × 240
1 × M10
SINAMICS G180 compact unit 690 V 6-pulse (230 to 600
1)
/690 V 3 AC TN/TT or IT system, 50 to 60 Hz)
7.5
6SE0100-1A.21-0.A7
2T2A-07600-007
4
16
Terminal
1
16
Terminal
4
16
Terminal
11
6SE0100-1A.21-3.A7
2T2A-07600-011
4
16
Terminal
1
16
Terminal
4
16
Terminal
15
6SE0100-1A.21-8.A7
2T2A-07600-015
4
16
Terminal
1
16
Terminal
4
16
Terminal
22
6SE0100-1A.22-5.A7
2T2A-07600-022
4
16
Terminal
1
16
Terminal
4
16
Terminal
30
6SE0100-1A.23-4.A7
2T2A-07600-030
2.5
120
1 × M8
2.5
35
Terminal
2.5
120
1 × M8
37
6SE0100-1A.24-2.A7
2T2A-07600-037
2.5
120
1 × M8
2.5
35
Terminal
2.5
120
1 × M8
45
6SE0100-1A.25-0.A7
2T2A-07600-045
2.5
120
1 × M8
2.5
35
Terminal
2.5
120
1 × M8
55
6SE0100-1A.25-8.A7
2T2A-07600-055
2.5
120
1 × M8
2.5
95
Terminal
2.5
120
1 × M8
75
6SE0100-1A.28-0.A7
2T2A-07600-075
2.5
120
1 × M8
2.5
95
Terminal
2.5
120
1 × M8
90
6SE0100-1A.31-0.A7
2T2A-07600-090
2.5
120
1 × M8
2.5
95
Terminal
2.5
120
1 × M8
110
6SE0100-1A.31-2.A7
2T2A-07600-110
2.5
120
1 × M8
2.5
95
Terminal
2.5
120
1 × M8
132
6SE0100-1A.31-4.A7
2T2A-07600-132
2.5
120
1 × M8
2.5
150
Terminal
2.5
120
1 × M8
160
6SE0100-1A.31-7.A7
2T2A-07600-160
2 × 6
2 × 240
1 × M10
2 × 6
2 × 240
1 × M10
200
6SE0100-1A.32-1.A7
2T2A-07600-200
2 × 6
2 × 240
1 × M10
2 × 6
2 × 240
1 × M10
1)
With an NRTL unit ("U" in 14th position of article number), the voltage range ends at max. 600 V, otherwise at 690 V.
© Siemens AG 2014