Option descriptions
标准选项
4/20
西门子D 18.1·2014
4
■
Options
(continued)
L80
CALOMAT CK145 without storage for motor temperature
prewarning
与凤凰社tion, the motor prewarning temperature limit is
monitored using up to 6 PTC thermistors. If the prewarning
超过温度,将警报输出到转换器。
故障未存储在calomat上,因此确实
不需要确认。
L81
Calomat CK145带有运动温度的存储空间
与凤凰社tion, the motor trip temperature limit is monitored
using up to 6 PTC thermistors. If the trip temperature is reached
an alarm is output to the converter. The converter switches itself
off. The fault is stored on the CALOMAT and therefore has to be
承认。
笔记:
When CALOMAT devices are used for switch-off, a line contactor
must be installed on the input side (option
S01
或者
S02
) 为了
遵守ATEX 95(指令94/9 EC)。
L82
CALOMAT CK145 without storage for transformer
预测温度
与凤凰社tion, the transformer prewarning temperature limit
is monitored using up to 6 PTC thermistors. If the prewarning
超过温度,将警报输出到转换器。
故障未存储在calomat上,因此确实
不需要确认。
L83
CALOMAT CK145 with storage for transformer
温度旅行
与凤凰社tion, the transformer trip temperature limit is
monitored using up to 6 PTC thermistors. If the trip temperature
is reached an alarm is output to the converter. The converter
关闭自身。故障存储在calomat上,然后 -
必须承认。
笔记:
When CALOMAT devices are used for switch-off, a line contactor
must be installed on the input side (option
S01
或者
S02
) 为了
遵守ATEX 95(指令94/9 EC)。
Apart from disconnecting the converter, it is also recommended
that the already existing tripping device on site is disconnected
连接到变压器的上游,例如
medium-voltage switch.
Y80
Calomat CK145用于其他PTC热敏电阻温度
监视功能
使用此选项,最多可以监视温度限制
6PTC thermistors. If the temperature limit is reached an alarm
输出到转换器。请指定是否故障
should be stored on the CALOMAT and therefore has to be
公认与否。
L87
Insulation monitoring
L87
用于操作的集成绝缘监视系统
secondary side of unit transformer in an IT system
L87
Insulation monitoring
An insulation monitor must be used if the converter is connected
到三锋变压器。绝缘监控器IRDH 275
从弯管器监视整个圆环耦合电路
绝缘断层。
此选项包括ded as standard fully wired up in the cabinet
用于用12脉冲和高脉冲转换的绝缘监测
单位变压器上的ers
grounded on the secondary
side.
功能:
所有循环耦合组件的绝缘抗性
(converter transformer secondary winding, cables, converter,
motor) is monitored by means of a measured signal that is
modulated onto the line supply. If the insulation resistance is
输出的情况下,输出警报或旅行消息。
Notice:
Only ONE insulation monitoring device at a time is permitted in
the entire galvanically coupled network. False tripping occurs if
2devices are used. This option is therefore only
suitable for
converter operation with one converter.