G02, G03, G04 and G05
Peripheral boards 1 to 4
Inadmissible option combinations
G02
,
G03
,
G04
and
G05
转换器的功能是智慧扩大h the
peripheral board. Every converter can be fitted or even retro-
fitted with one of these peripheral boards.
Boards with safety-related inputs (PTC thermistor or the function
"Safe Torque Off") are only permitted to be retrofitted by our
authorized qualified personnel.
In addition to the main board, peripheral boards 2 and 4 are also
expanded by a daughterboard which contains the circuitry for
the PTC thermistor inputs.
G02
Peripheral board 1
G02
Peripheral board 1
Option
G02
(peripheral board 1) provides in addition to standard
converter terminals:
•
2 analog outputs (AO)
4 to 20 mA/0 to 10 V
Standard assignment of inputs/outputs
The table below provides an overview of the pre-assignment
function of interfaces in the pin assignments for the "Standard"
application.
G02
Circuit diagram for peripheral board 1
外围板1…4
G02
G03
G04
G05
Peripheral board 1
G02
–
–
–
Peripheral board 2
G03
–
–
–
Peripheral board 3
G04
–
–
–
Peripheral board 4
G05
–
–
–
–
Options mutually exclude each other.
Peripheral board
1
2
3
4
2 PTC thermistor inputs for ATEX-certified motor
temperature monitoring for motors in hazardous
zones (prewarning/trip)
One input "Safe Torque Off" acc. to
EN ISO 13849-1,
Cat. 3. PL d or SIL 2 acc. to EN 61508
9 digital inputs (DI)
3 relay outputs (DO)
2 analog outputs (AO)
24 V / 300 mA power supply unit
Signal designation
Function
Internal PTC thermistor
input 90, 91, 92, 93
Not assigned
Internal analog output 64, 65
Torque
Internal analog output 66, 67
Power
66
67
93
91
92
90
64
65
-X2:
-X3:
AO 3 X2: 64
AO 3 X2: 65
AO 4 X2: 66
AO 4 X2: 67
G02
Peripheral board 1
Analog output 3
Analog output 4
0 …10 V or 0 (4)...20 mA
0 …10 V or 0 (4)...20 mA
M_ATV
G_D024_EN_00005
Not assigned