SIEMENS
3/9
Siemens D 11 · 2015
■
Technical specifications
(continued)
3
SINAMICS G130
Drive converter chassis units
75 kW to 800 kW
Deviations from the specified classes are underlined
.
Electrical specifications
(continued)
Rated short-circuit current
according to IEC, in conjunction with
the specified fuses
• 1.1 … 447 kW
65 kA
• 448 ... 671 kW
84 kA
• 672 ... 1193 kW
170 kA
• > 1194 kW
200 kA
Rated short-circuit current SCCR
(Short Circuit Current Rating) according
to UL508C (up to 600 V), in conjunction
with the specified fuses or circuit
breakers
• 1.1 … 447 kW
65 kA
• 448 ... 671 kW
84 kA
• 672 ... 1193 kW
170 kA
• > 1194 kW
200 kA
Control method
Vector control with and without encoder or V/f control
Fixed speeds
15 fixed speeds plus 1 minimum speed, parameterizable
(in the default setting, 3 fixed setpoints plus 1 minimum speed are selectable using terminal block / PROFIBUS)
Speed ranges that can be skipped
4, parameterizable
Setpoint resolution
0.001 rpm数字
12-bit analog
Braking operation
By means of additional Braking Modules and braking resistors
Mechanical specifications
Degree of protection
IP00 or IP20 depending on type
Protection class
I according to EN 61800-5-1
Touch protection
EN 50274 / BGV A3 when used for the intended purpose
Cooling method
Forced air cooling AF according to EN 60146
环境条件ns
Storage
Transport
Operation
Ambient temperature
-25 ... +55° C
-25 ... +70° C
as of -40° C
for 24 hours
0
... +40° C
up to +55° C
see derating data
Relative humidity
(condensation not permissible)
5 ... 95%
5 ... 95%
at 40° C
5 ... 95%
Class 1K4 according to EN 60721-3-1
Class 2K3 according to EN 60721-3-2
Class 3K3 according to EN 60721-3-3
Environmental class /
harmful chemical substances
Class 1C2 according to EN 60721-3-1
Class 2C2 according to EN 60721-3-2
Class 3C2 according to EN 60721-3-3
Organic/biological influences
Class 1B1 according to EN 60721-3-1
Class 2B1 according to EN 60721-3-2
Class 3B1 according to EN 60721-3-3
Degree of pollution
2 according to EN 61800-5-1
Installation altitude
Up to 2000 m above sea level without derating; > 2000 m
see derating data
Mechanical stability
Storage
Transport
Operation
Vibratory load
• Deflection
1.5 mm at 5
... 9 Hz
3.1 mm
at 5
... 9 Hz
0.075 mm at 10 ... 58 Hz
• Acceleration
5 m/s
2
at > 9 ... 200 Hz
10 m/s
2
at > 9 ... 200 Hz
10 m/s
2
at > 58 … 200 Hz
Class 1M2 according to EN 60721-3-1
Class 2M2 according to EN 60721-3-2
–
Shock load
• Acceleration
40 m/s
2
for 22 ms
100米/秒
2
for 11 ms
100米/秒
2
for 11 ms
Class 1M2 according to EN 60721-3-1
Class 2M2 according to EN 60721-3-2
Class 3M4 according to EN 60721-3-3
Compliance with standards
CE marking
根据电磁兼容指令2004/108 / EC和低Voltage Directive No. 2006/95/EC and Machinery Directive
No. 2006/42/EC for functional safety.
Radio interference suppression
The SINAMICS G130 converter systems are not designed for connection to the public power network
("first environment"). Radio interference suppression is compliant with the EMC product standard for variable-speed
drives EN 61800-3, "Second environment" (industrial networks). EMC disturbances can occur when connected to the
public power networks. However, if additional measures are taken (e.g. line filter), it can also be operated in the
"first environment".
2)
Approvals
cULus (only for 380 ... 480 V 3 AC and 500 ... 600 V 3 AC)
1)
The output frequency is also affected by the selected control method and
the pulse frequency.
For further information, please refer to the SINAMICS
Low Voltage Engineering Manual.
2)
Applies to motor cable lengths < 100 m.
© Siemens AG 2015