SIEMENS
4/44
Siemens D 11 · 2015
4
SINAMICS G150
Drive converter cabinet units
Line-side power components > Recommended fuses
■
Selection and ordering data
The fuses specified below are the recommended types for pro-
tecting the unit on the low-voltage distribution panel. If option
L26
(main switch or circuit breaker) has been selected, the con-
verter already has integrated semiconductor protection. In this
case, a fuse of type 3NA can be used on the distribution panel.
If option
L26
has not been selected, we strongly advise that
type 3NE fuses are used
1)
.
Further information on the fuses is provided in Catalog LV 10.
Single connection
Note:
The power data in hp units is based on the NEC/CEC stan-
达尔德人的北美市场。
Type rating
SINAMICS G150 con-
verter cabinet units
Fuse
with
existing fuse switch disconnector
(option L26)
Fuse
(incl. semiconductor protection)
without
fuse switch disconnector
at 50 Hz,
400 V, 500 V
or 690 V
at 60 Hz,
460 V or
575 V
Versions A and C
Rated current
Frame size acc.
to IEC 60269-2
Rated current
Frame size acc.
to IEC 60269-2
kW
hp
6SL3710-...
Article No.
A
Article No.
A
3.80 ... 480 V 3 AC
110
150
1GE32-1 . A3
3.NA3144
250
2
3.NE1230-2
315
1
132
200
1GE32-6 . A3
3.NA3250
3.00
2
3.NE1331-2
3.50
2
160
250
1GE33-1 . A3
3.NA3254
3.55
3.
3.NE1334-2
500
2
200
3.00
1GE33-8 . A3
3.NA3260
400
3.
3.NE1334-2
500
2
250
400
1GE35-0 . A3
3.NA3372
630
3.
3.NE1436-2
630
3.
315
500
1GE36-1 . A3
3.NA3475
800
4
3.NE1438-2
800
3.
400
600
1GE37-5 . A3
3.NA3475
800
4
3.NE1448-2
850
3.
450
600
1 ge38-4。A3
3.NA3365
2 × 500
3.
3.NE1436-2
2 × 630
3.
560
800
1GE41-0 . A3
3.NA3472
2 × 630
3.
3.NE1437-2
2 × 710
3.
500 ... 600 V 3 AC
110
150
1GF31-8 . A3
3.NA3244-6
250
2
3.NE1227-2
250
1
132
200
1GF32-2 . A3
3.NA3252-6
315
2
3.NE1230-2
315
1
160
250
1GF32-6 . A3
3.NA3354-6
3.55
3.
3.NE1331-2
3.50
2
200
3.00
1GF33-3 . A3
3.NA3365-6
500
3.
3.NE1334-2
500
2
250
400
1GF34-1 . A3
3.NA3365-6
500
3.
3.NE1334-2
500
2
315
450
1GF34-7 . A3
3.NA3352-6
2 × 315
3.
3.NE1435-2
560
3.
400
500
1GF35-8 . A3
3.NA3354-6
2 × 355
3.
3.NE1447-2
670
3.
500
700
1GF37-4 . A3
3.NA3365-6
2 × 500
3.
3.NE1448-2
850
3.
560
800
1GF38-1 . A3
3.NA3365-6
2 × 500
3.
3.NE1343-2
2 × 500
2
660 ... 690 V 3 AC
75
1GH28-5 . A3
3.NA3132-6
125
1
3.NE1022-2
125
00
90
1GH31-0 . A3
3.NA3132-6
125
1
3.NE1022-2
125
00
110
1GH31-2 . A3
3.NA3136-6
160
1
3.NE1224-2
160
1
132
1GH31-5 . A3
3.NA3240-6
200
2
3.NE1225-2
200
1
160
1GH31-8 . A3
3.NA3244-6
250
2
3.NE1227-2
250
1
200
1GH32-2 . A3
3.NA3252-6
315
2
3.NE1230-2
315
1
250
1GH32-6 . A3
3.NA3354-6
3.55
3.
3.NE1331-2
3.50
2
315
1GH33-3 . A3
3.NA3365-6
500
3.
3.NE1334-2
500
2
400
1GH34-1 . A3
3.NA3365-6
500
3.
3.NE1334-2
500
2
450
1GH34-7 . A3
3.NA3352-6
2 × 315
3.
3.NE1435-2
560
3.
560
1GH35-8 . A3
3.NA3354-6
2 × 355
3.
3.NE1447-2
670
3.
710
1GH37-4 . A3
3.NA3365-6
2 × 500
3.
3.NE1448-2
850
3.
800
1GH38-1 . A3
3.NA3365-6
2 × 500
3.
3.NE1334-2
2 × 500
2
1)
The double function fuses (3NE1) with operating class gS for cable and
semiconductor protection are recommended to protect the converter.
These fuses are specially adapted to the requirements of the semiconduc-
tors in the input rectifier
– Superfast
– Adapted to the limit current integral of the semiconductor
– Lower arc voltage
– Improved current limiting
© Siemens AG 2015