SIEMENS
4/40
Siemens D 11 · 2015
■
Characteristic curves
(continued)
4
SINAMICS G150
Drive converter cabinet units
75 kW to 2700 kW
Overload capability
The SINAMICS G150 converter cabinet units have an overload
reserve in order to overcome breakaway torques, for example. If
larger surge loads occur, this must be taken into account in the
配置。与过载requiremen驱动器ts, the appro-
priate base load current must, therefore, be used as a basis for
the required load.
The criterion for overload is that the drive is operated with its
base load current before and after the overload occurs on the
basis of a duty cycle duration of 300 s.
The base load current for a low overload
I
L
is based on a duty
cycle of 110% for 60 s or 150% for 10 s.
The base load current for a high overload
I
H
is based on a duty
cycle of 150% for 60 s or 160% for 10 s.
Low overload
High overload
60 s
10 s
300 s
t
1.1 x
I
L
1.5 x
I
L
Short-time current 110 %
Short-time current 150 %
Rated current (continuous)
Converter current
G_D213_EN_00035
Base-load current
I
L
for low overload
I
L
I
rated
60 s
10 s
t
1.5 x
I
H
1.6 x
I
H
Short-time current 160 %
Short-time current 150 %
Rated current (continuous)
Converter current
G_D213_EN_00036
Base-load current
I
H
for high overload
I
H
I
rated
300 s
© Siemens AG 2015