SIEMENS
4/23
Siemens D 35 · 2017
■
Technical specifications
(continued)
4
SINAMICS G120P built-in and wall-mounted units
PM230 Power Modules, 0.37 kW to 90 kW
PM230 Power Modules
Line voltage 380 ... 480 V 3 AC
PM230 Power Modules degree of protection IP20 standard variant
Without integrated line filter
6SL3210-1NE27-5UL0
6SL3210-1NE28-8UL0
6SL3210-1NE31-1UL0
6SL3210-1NE31-5UL0
With integrated line filter class A
6SL3210-1NE27-5AL0
6SL3210-1NE28-8AL0
6SL3210-1NE31-1AL0
6SL3210-1NE31-5AL0
Output current
at 50 Hz 400 V 3 AC
• Rated current
I
rated
1)
A
75
90
110
145
• Base-load current
I
L
1)
A
75
90
110
145
• Base-load current
I
H
2)
A
60
75
90
110
• Maximum current
I
max
A
90
112
135
165
Rated power
• Based on
I
L
kW
37
45
55
75
• Based on
I
H
kW
30
37
45
55
Rated pulse frequency
kHz
4
4
4
4
Efficiency
η
%
97
97
97
97
Power loss
3)
at rated current
kW
0.791
0.976
1.237
1.69
Cooling air requirement
m
3
/s (ft
3
/s)
0.08 (2.8)
0.08 (2.8)
0.15 (5.3)
0.15 (5.3)
Sound pressure level
L
pA
(1 m)
dB
<60
<60
<60
<60
24 V DC power supply
for Control Unit
A
1
1
1
1
Input current
4)
• Rated current
A
70
84
102
135
• Based on
I
H
A
56
70
84
102
Line supply connection
U1/L1, V1/L2, W1/L3
M6 screw studs
M6 screw studs
M8 screw studs
M8 screw studs
• Conductor cross-section
mm
2
25 ... 50
25 ... 50
35 ... 120
35 ... 120
Motor connection
U2, V2, W2
M6 screw studs
M6 screw studs
M8 screw studs
M8 screw studs
• Conductor cross-section
mm
2
25 ... 50
25 ... 50
35 ... 120
35 ... 120
Motor cable length, max.
5)
• Shielded
m (ft)
25 (82)
25 (82)
25 (82)
25 (82)
• Unshielded
m (ft)
100 (328)
100 (328)
100 (328)
100 (328)
Degree of protection
IP20
IP20
IP20
IP20
Dimensions
• Width
mm (in)
275 (10.83)
275 (10.83)
350 (13.78)
350 (13.78)
• Height
-
Without integrated line filter
mm (in)
499 (19.65)
499 (19.65)
634 (24.96)
634 (24.96)
-
With integrated line filter
mm (in)
635 (25)
635 (25)
934 (36.77)
934 (36.77)
• Depth
-
Without operator panel
mm (in)
204 (8.03)
204 (8.03)
316 (12.44)
316 (12.44)
-
With operator panel, max.
mm (in)
275 (10.83)
275 (10.83)
387 (15.24)
387 (15.24)
Frame size
FSE
FSE
FSF
FSF
Weight, approx.
• Without integrated line filter
kg (lb)
15 (33.1)
15 (33.1)
34 (74.97)
34 (74.97)
• With integrated line filter
kg (lb)
22 (48.5)
22 (48.5)
46 (101.43)
46 (101.43)
1)
The rated output current
I
rated
and the base-load current
I
L
are based on
the duty cycle for low overload (LO).
2)
The base-load current
I
H
基于高过载的工作周期吗
(HO).
3)
Typical values. You can find more information on the Internet at
4)
The input current depends on the motor load and line impedance and
applies for a line impedance corresponding to
u
K
= 1 %. The rated input
currents apply for a load at rated power (based on
I
rated
) – these current
values are specified on the rating plate.
5)
Max. motor cable length 25 m (82 ft) (shielded) for PM230 Power Modules
with integrated line filter to maintain the limit values acc. to EN 61800-3
Category C2. With unshielded cables, Category C2 is not achieved.
© Siemens AG 2017