SIEMENS
4/8
Siemens D 35 · 2017
■
Technical specifications
(continued)
4
SINAMICS G120P built-in and wall-mounted units
Control Units
CU230P-2 Control Units
Control Unit
CU230P-2 HVAC
CU230P-2 DP
CU230P-2 PN
6SL3243-0BB30-1HA3
6SL3243-0BB30-1PA3
6SL3243-0BB30-1FA0
Tool interfaces
Memory card
SINAMICS SD card
Operator panels
• Intelligent Operator Panel IOP
Can be directly plugged on
• Basic Operator Panel BOP-2
Can be directly plugged on
• Blanking cover
Required when no operator panel is plugged in order to achieve degree of protection IP55 on PM230
Power Modules degree of protection IP55/UL Type 12
PC interface
USB (connection via PC inverter connection kit 2)
Open-loop/closed-loop control techniques
U/f linear/quadratic/parameterizable
U/f with flux current control (FCC)
U/f ECO; linear/quadratic
Vector control, sensorless
Software functions
Setpoint input
Fixed frequencies
16, parameterizable
JOG
Digital motorized potentiometer (MOP)
Ramp smoothing
Extended ramp-function generator
(with ramp smoothing OFF3)
Slip compensation
Signal interconnection with BICO technology
Free function blocks (FFB)
for logical and arithmetic operations
Switchable drive data sets (DDS)
(4)
Switchable command data sets (CDS)
(4)
Flying restart
Automatic restart
after line supply failure or operating fault (AR)
Technology controller (internal PID)
Hibernation mode
with internal/external PID controller
Belt monitoring
有和没有传感器(负载转矩监测)
Dry-running/overload protection monitoring
(load torque monitoring)
Thermal motor protection
(
I
2
t
, sensor: PTC/Pt1000/KTY/bimetal)
Thermal inverter protection
Motor identification
Auto-ramping (
V
dcmax
controller)
Kinetic buffering (
V
dcmin
controller)
Possible braking functions
• DC braking (PM230, PM240P-2, PM330, Cabinet)
• Compound braking (PM240P-2)
• Dynamic braking with optional Braking Module and braking resistor (PM330, Cabinet)
© Siemens AG 2017