SIEMENS
3/10
Siemens D 35 · 2017
■
Technical specifications
(continued)
3
System configuration
SINAMICS G120P and SINAMICS G120P Cabinet pump, fan, compressor converters
SINAMICS G120P and SINAMICS G120P Cabinet pump, fan, compressor converters
Ambient conditions
Protection class
According to EN 61800-5-1
Class I (with protective conductor system) and class III (PELV)
Touch protection
According to EN 50274 and DGUV Regulation 3 when used for the intended purpose
Permissible ambient and coolant temperature (air)
during operation for line-side power components and
Power Modules
• Low overload (LO)
Frame sizes FSA to FSC: -10 ... +40 °C (14 ... 104 °F) without derating
帧大小FSD FSF (PM230): 0 ... 40 °C (32 ... 104 °F) without derating
帧大小FSD FSF (PM240P-2): -20 ... +40 °C (-4 ... +104 °F) without derating
Frame sizes FSA to FSF: >40 ... 60 °C (>104 ... 140 °F)
see derating characteristics
Frame sizes GX to JX: 0 ... 45 °C (32 ... 113 °F) without derating
>45 ... 55 °C (>113 ... 131 °F)
see derating characteristics
SINAMICS G120P Cabinet: 0 ... 40 °C (32 ... 104 °F) without derating
>40 ... 50 °C (>104 ... 122 °F)
see derating characteristics
• High overload (HO)
Frame sizes FSA to FSC: -10 ... +50 °C (14 ... 122 °F) without derating
帧大小FSD FSF (PM230): 0 ... 50 °C (32 ... 122 °F) without derating
帧大小FSD FSF (PM240P-2): -20 ... +50 °C (-4 ... +122 °F) without derating
>50 ... 60 °C (>122 ... 140 °F)
see derating characteristics
Frame sizes GX to JX: 0 ... 45 °C (32 ... 113 °F) without derating
>45 ... 55 °C (>113 ... 131 °F)
see derating characteristics
SINAMICS G120P Cabinet: 0 ... 40 °C (32 ... 104 °F) without derating
>40 ... 50 °C (>104 ... 122 °F)
see derating characteristics
Installation altitude
Up to 1000 m (3281 ft) above sea level without derating,
> 1000 m (3281 ft)
see derating characteristics
Permissible ambient and coolant temperature (air)
during operation for Control Units and supplementary
system components
With CU230P-2 HVAC/DP with/without blanking cover: -10 ... +60 °C (14 ... 140 °F)
With CU230P-2 PN with/without blanking cover: -10 ... +55 °C (14 ... 131 °F)
With IOP/BOP-2: 0 ... 50 °C (32 ... 122 °F)
Derating of 3 K/1000 m applies to Control Units as of an installation altitude of 1000 m (3281 ft)
above sea level.
Climatic ambient conditions
• Storage
1)
acc. to EN 60721-3-1
-
Drives and components, frame sizes FSA to FSF for
PM230
Temperature -40 ... +70 °C (-40 ... +158 °F)
Relative air humidity <95 %, condensation not permissible
-
Drives and components, frame sizes FSD to FSF for
PM240P-2
Class 1K3
Temperature -25 ... +55 °C (-13 ... +131 °F)
Relative air humidity 5 ... 95 %, condensation not permissible
-
Drives and components, frame sizes GX to JX and
SINAMICS G120P Cabinet
Class 1K4
Temperature -25 ... +55 °C (-13 ... +131 °F)
Relative air humidity 5 ... 95 %, condensation not permissible
• Transport
1)
acc. to EN 60721-3-2
-
Drives and components, frame sizes FSA to FSF
Class 2K4
Temperature -40 ... +70 °C (-40 ... +158 °F)
Max. air humidity 95 % at 40 °C (104 °F)
-
Drives and components, frame sizes GX to JX and
SINAMICS G120P Cabinet
Class 2K3
Temperature -25 ... +70 °C (-13 ... +158 °F), -40 °C (-40 °F) permissible for 24 h
Relative air humidity 5 ... 95 % at 40 °C (104 °F)
• Operation acc. to EN 60721-3-3
-
Drives and components, frame sizes FSA to FSF
Class 3K3
Condensation, splashwater, and ice formation not permitted (EN 60204, Part 1)
-
Drives and components, frame sizes GX to JX
Class 3K3
Temperature 0 ... 45 °C (32 ... 113 °F), up to 55 °C (131 °F) with derating
Relative air humidity 5 ... 95 %
Condensation, splashwater and ice formation are not permitted (EN 60204, Part 1)
-
SINAMICS G120P Cabinet
Class 3K3
Temperature 0 ... 40 °C (32 ... 104 °F), up to 50 °C (122 °F) with derating
Relative air humidity 5 ... 95 %
Condensation, splashwater and ice formation are not permitted (EN 60204, Part 1)
Environmental class/harmful chemical substances
• Storage
1)
acc. to EN 60721-3-1
Class 1C2
• Transport
1)
acc. to EN 60721-3-2
2C2类
• Operation acc. to EN 60721-3-3
Class 3C2
Organic/biological influences
• Storage
1)
acc. to EN 60721-3-1
Class 1B1
• Transport
1)
acc. to EN 60721-3-2
Class 2B1
• Operation acc. to EN 60721-3-3
Class 3B1
Degree of pollution
According to EN 61800-5-1
2
1)
In transport packaging.
© Siemens AG 2017