SIEMENS
5/26
Siemens D 35 · 2017
■
Technical specifications
(continued)
5
SINAMICS G120P Cabinet, converter cabinet units
SINAMICS G120P Cabinet, 75 kW to 630 kW
SINAMICS G120P Cabinet
Note:
The power data in hp units are based on the NEC/CEC stan-
达尔德人的北美市场。
Information on the line connection, motor connection and cabi-
net grounding can be found in section Cable cross-sections and
connections.
Line voltage 500 ... 690 V 3 AC
SINAMICS G120P Cabinet converter cabinet units
6SL3710-1PG33-7 . A0-Z
6SL3710-1PG34-0 . A0-Z
6SL3710-1PG34-5 . A0-Z
6SL3710-1PG35-2 . A0-Z
Rated power
• At
I
L
690 V/50 Hz
1)
kW
315
355
400
450
• At
I
L
575 V/60 Hz
2)
hp
350
400
450
450
• At
I
H
690 V/50 Hz
1)
kW
250
315
355
400
• At
I
H
575 V/60 Hz
2)
hp
250
300
350
450
Output current
• Rated current
I
rated
(500 V ±10 %)
A
368
400
453
516
• Rated current
I
rated
(600 V±10%)
A
353
396
441
497
• Rated current
I
rated
(690 V ±10 %)
A
340
393
430
480
• Base-load current
I
L
(500 V ±10 %)
3)
A
361
392
443
505
• Base-load current
I
L
(690 V ±10 %)
3)
A
330
385
420
470
• Base-load current
I
H
(500 V ±10 %)
4)
A
295
320
367
423
• Base-load current
I
H
(690 V ±10 %)
4)
A
272
314
348
394
• Output current, max.
A
487
529
598
682
Input current
• Rated current
I
rated
(500 V ±10 %)
5)
A
383
416
471
537
• Rated current
I
rated
(600 V±10%)
5)
A
367
412
459
517
• Rated current
I
rated
(690 V ±10 %)
5)
A
354
409
447
499
• Base-load current
I
L
(500 V ±10 %)
3)
A
375
408
461
526
• Base-load current
I
L
(690 V ±10 %)
3)
A
343
401
437
489
• Base-load current
I
H
(500 V ±10 %)
4)
A
307
333
381
440
• Base-load current
I
H
(690 V ±10 %)
4)
A
283
327
362
410
• Input current, max.
A
507
550
623
710
Current requirement,
24 V DC auxiliary power supply
6)
• Version A
A
1.0
1.0
1.0
1.0
• Version C
A
0.5
0.5
0.5
0.5
Short-circuit current rating acc. to IEC
in conjunction with the specified fuses
without/with option L26
kA
65/65
65/50
65/50
65/50
Minimum short-circuit current
7)
• For 3NE1 fuses
A
3500
4500
7000
8500
• For 3NA3 fuses
A
10000
10500
13000
14600
Power loss, max.
at
I
rated
(500 V/40 °C), without options
kW
5.838
6.665
7.429
8.259
冷却剂
Air
Air
Air
Air
冷却剂requirements
m
3
/秒
(ft
3
/秒)
0.6 (21.2)
0.6 (21.2)
0.6 (21.2)
0.6 (21.2)
Sound pressure level
L
pA
(1 m)
at 50/60 Hz
• Version A/C
dB
69/69
69/69
69/69
69/69
Cable length, max.
between Power Module and motor
• When compliant with Categories C2
and C3 according to EN 61800-3
shielded
m (ft)
150 (492)
150 (492)
150 (492)
150 (492)
• When non-compliant with the limit
values for RI suppression and
without output reactor; unshielded
m (ft)
200 (656)
200 (656)
200 (656)
200 (656)
• When non-compliant with the limit
values for RI suppression with output
reactor; shielded/unshielded
m (ft)
300/450 (984/1476)
300/450 (984/1476)
300/450 (984/1476)
300/450 (984/1476)
Dimensions
• Width for
version A/C
mm (in)
1200 (47.24)
1200 (47.24)
1200 (47.24)
1200 (47.24)
• Height
8)
mm (in)
2000 (78.74)
2000 (78.74)
2000 (78.74)
2000 (78.74)
• Depth
mm (in)
600 (23.62)
600 (23.62)
600 (23.62)
600 (23.62)
Frame size
HX
HX
HX
HX
Weight
Versions A/C
(degree of protection IP20, w/o options)
kg (lb)
515/435 (1135/959)
522/442 (1151/974)
522/442 (1151/974)
535/455 (1179/1003)
1)
Rated power of a typ. 4-pole standard induction motor based on base-load
current
I
L
or
I
H
at 690 V 3 AC/50 Hz.
2)
Rated power of a typ. 4-pole standard induction motor based on base-load
current
I
L
or
I
H
at 575 V 3 AC/60 Hz.
3)
The base-load current
I
L
is based on a duty cycle of 110 % for 60 s or
135 % for 3 s with a duty cycle duration of 300 s
(see overload capability
characteristics)
.
4)
The base-load current
I
H
is based on a duty cycle of 150 % for 60 s with
a duty cycle duration of 300 s
(see overload capability characteristics)
.
5)
The current values given here are based on the rated output current.
6)
If the drive closed-loop control is still to remain active when the main line
supply fails, then the converter must be provided with an external 24 V DC
supply.
7)
10 ms value from current-time characteristic for reliable tripping of installed
protection devices. If the minimum short-circuit current is not reached, the
tripping time of the fuses is increased, which can lead to damage.
8)
The cabinet height increases by 300 mm (11.8 in) for degrees of protection
IP20 and IP21, and by 400 mm (15.7 in) for degrees of protection IP23,
IP43 and IP54.
© Siemens AG 2017