Technical specifications
(continued)
5
SINAMICS G120P Cabinet, converter cabinet units
SINAMICS G120P Cabinet, 75 kW to 630 kW
SINAMICS G120P Cabinet
Note:
The power data in hp units are based on the NEC/CEC stan-
达尔德人的北美市场。
Information on the line connection, motor connection and cabi-
net grounding can be found in section Cable cross-sections and
connections.
Line voltage 380 ... 480 V 3 AC
SINAMICS G120P Cabinet converter cabinet units
6SL3710-
1PE33-0.A0-Z
6SL3710-
1PE33-7.A0-Z
6SL3710-
1PE34-6.A0-Z
6SL3710-
1PE35-8.A0-Z
6SL3710-
1PE36-6.A0-Z
6SL3710-
1PE37-4.A0-Z
Rated power
• At
I
L
400 V/50 Hz
1)
kW
160
200
250
315
355
400
• At
I
L
460 V/60 Hz
2)
hp
200
250
300
400
450
500
• At
I
H
400 V/50 Hz
1)
kW
132
160
200
250
250
315
• At
I
H
460 V/60 Hz
2)
hp
150
200
200
300
300
350
Output current
• Rated current
I
rated
(400 V ±10 %)
A
300
370
460
585
655
735
• Rated current
I
rated
(480 V ±10 %)
A
245
308
369
487
526
602
• Base-load current
I
L
(400 V ±10 %)
3)
A
290
360
450
570
640
720
• Base-load current
I
L
(480 V ±10 %)
3)
A
240
302
361
477
515
590
• Base-load current
I
H
(400 V ±10 %)
4)
A
240
296
368
468
491
551
• Base-load current
I
H
(480 V ±10 %)
4)
A
196
247
295
390
394
452
• Output current, max.
A
392
486
608
770
864
972
Input current
• Rated current
I
rated
(400 V ±10 %)
5)
A
317
375
469
597
668
750
• Rated current
I
rated
(480 V ±10 %)
5)
A
262
314
376
497
536
614
• Base-load current
I
L
(400 V ±10 %)
3)
A
307
365
459
585
654
735
• Base-load current
I
L
(480 V ±10 %)
3)
A
257
308
368
486
525
602
• Base-load current
I
H
(400 V ±10 %)
4)
A
254
300
375
477
501
562
• Base-load current
I
H
(480 V ±10 %)
4)
A
210
251
301
397
402
461
• Input current, max.
A
415
493
620
785
881
992
Current requirement,
24 V DC auxiliary power supply
6)
• Version A
A
1
1
1
1
1
1
• Version C
A
0.5
0.5
0.5
0.5
0.5
0.5
Short-circuit current rating acc. to IEC
in conjunction with the specified fuses
without/with option L26
kA
65/65
65/65
65/50
65/50
65/50
65/50
Minimum short-circuit current
7)
• For 3NE1 fuses
A
3500
4500
7000
10000
11000
13000
• For 3NA3 fuses
A
9500
14000
20000
20000
30000
30000
Power loss, max.
at
I
rated
(400 V/40 °C), without options
kW
4.01
4.871
5.683
7.358
8.287
9.101
Coolant
Air
Air
Air
Air
Air
Air
Coolant requirements
m
3
/s
(ft
3
/s)
0.21 (7.42)
0.21 (7.42)
0.21 (7.42)
0.6 (21.2)
0.6 (21.2)
0.6 (21.2)
Sound pressure level
L
pA
(1 m)
at 50/60 Hz
• Version A
dB
66/66
66/66
66/66
69/69
69/69
69/69
• Version C
dB
63/63
63/63
63/63
66/66
66/66
66/66
Cable length, max.
between Power Module and motor
• When compliant with Categories C2
and C3 according to EN 61800-3
shielded
m (ft)
150 (492)
150 (492)
150 (492)
150 (492)
150 (492)
150 (492)
• When non-compliant with the limit
values for RI suppression and
without output reactor; unshielded
m (ft)
200 (656)
200 (656)
200 (656)
200 (656)
200 (656)
200 (656)
• When non-compliant with the limit
values for RI suppression with output
reactor; shielded/unshielded
m (ft)
300/450
(984/1476)
300/450
(984/1476)
300/450
(984/1476)
300/450
(984/1476)
300/450
(984/1476)
300/450
(984/1476)
Dimensions
• Width for version A/C
mm (in)
1000/600
(39.37/23.62)
1000/600
(39.37/23.62)
1000/600
(39.37/23.62)
1200
9)
/800
(47.24
9)
/31.50)
1200
9)
/800
(47.24
9)
/31.50)
1200
9)
/800
(47.24
9)
/31.50)
• Height
8)
mm (in)
2000 (78.74)
2000 (78.74)
2000 (78.74)
2000 (78.74)
2000 (78.74)
2000 (78.74)
• Depth
mm (in)
600 (23.62)
600 (23.62)
600 (23.62)
600 (23.62)
600 (23.62)
600 (23.62)
Frame size
GX
GX
GX
HX
HX
HX
Weight
Versions A/C (degree of protection
IP20, without options)
kg (lb)
370/290
(816/639)
380/300
(838/661)
400/300
(882/661)
500/430
(1102/948)
500/440
(1102/970)
530/440
(1169/970)
1)
Rated power of a typ. 4-pole standard induction motor based on base-load
current
I
L
or
I
H
at 400 V 3 AC/50 Hz.
2)
Rated power of a typ. 4-pole standard induction motor based on base-load
current
I
L
or
I
H
at 460 V 3 AC/60 Hz.
3)
The base-load current
I
L
is based on a duty cycle of 110 % for 60 s or 135 %
3 s和300年代的工作周期时间
(see overload capability character-
istics)
.
4)
The base-load current
I
H
is based on a duty cycle of 150 % for 60 s with a duty
cycle duration of 300 s
(see overload capability characteristics)
.
5)
The current values given here are based on the rated output current.
6)
If the drive closed-loop control is still to remain active when the main line sup-
ply fails, then the converter must be provided with an external 24 V DC supply.
7)
10 ms value from current-time characteristic for reliable tripping of installed
protection devices. If the minimum short-circuit current is not reached, the
tripping time of the fuses is increased, which can lead to damage.
8)
The cabinet height increases by 300 mm (11.81 in) for IP21 degree of protec-
tion, and by 400 mm (15.75 in) for IP23, IP43 and IP54 degrees of protection.
9)
The specified cabinet widths increase depending on the options selected.
For details, see description of option
L01
.