SIEMENS
4/67
Siemens D 35 · 2017
■
Technical specifications
(continued)
4
SINAMICS G120P built-in and wall-mounted units
PM330 Power Modules, 160 kW to 630 kW
PM330 Power Modules
Line voltage 500 ... 690 V 3 AC
PM330 Power Modules
6SL3310-1PG35-8AA0
6 sl3310-1pg36-5aa0
6SL3310-1PG37-2AA0
Rated power
1)
• Based on the base-load current
I
L
-
At 690 V/50 Hz
kW
500
560
630
-
At 575 V/60 Hz
hp
500
600
700
• Based on the base-load current
I
H
-
At 690 V/50 Hz
kW
450
500
560
-
At 575 V/60 Hz
hp
450
500
500
Output current
at 50 Hz 3 AC
• Rated current
I
rated
(500 V ±10 %)
A
581
654
725
• Rated current
I
rated
(600 V ±10 %)
A
557
623
693
• Rated current
I
rated
(690 V ±10 %)
A
535
595
665
• Base-load current
I
L
(500 V ±10 %)
2)
A
569
640
710
• Base-load current
I
L
(690 V ±10 %)
2)
A
520
580
650
• Base-load current
I
H
(500 V ±10 %)
3)
A
482
523
580
• Base-load current
I
H
(690 V ±10 %)
3)
A
444
476
532
• Max. output current
I
max
A
768
864
959
Rated pulse frequency
kHz
2
2
2
Input current
4)
• Rated current
I
rated
(500 V ±10 %)
A
596
679
753
• Rated current
I
rated
(600 V ±10 %)
A
578
647
720
• Rated current
I
rated
(690 V ±10 %)
A
555
618
690
• Base-load current
I
L
(500 V ±10 %)
2)
A
591
665
737
• Base-load current
I
L
(690 V ±10 %)
2)
A
540
602
675
• Base-load current
I
H
(500 V ±10 %)
3)
A
501
543
602
• Base-load current
I
H
(690 V ±10 %)
3)
A
461
494
552
• Max. input current
A
798
897
995
Short-circuit current rating
根据to IEC
与指定的保险丝
kA
100
100
100
Rated short-circuit current SCCR
(短期Circuit Current Rating)
in accordance with UL 61800-5-1
(up to 600 V)
与指定的保险丝
kA
100
100
100
Minimum short-circuit current
5)
• For 3NE1 fuses
A
10000
11000
13000
Efficiency
η
at rated current
I
rated
(690 V/45 °C (113 °F))
%
98.3
98.3
98.3
Power loss
at rated current
I
rated
(690 V/45 °C (113 °F))
kW
8.134
8.828
9.937
Coolant requirements
m
3
/s (ft
3
/s)
0.45 (15.9)
0.45 (15.9)
0.45 (15.9)
Coolant
Air
Air
Air
Sound pressure level
L
pA
(1 m)
dB
74
74
74
Power requirement 24 V DC supply
A
0.5
0.5
0.5
1)
Rated power of a typical 4-pole standard induction motor based on the
base-load current
I
L
or
I
H
at 690 V 3 AC/50 Hz (kW) or 575 V 3 AC/60 Hz
(hp).
2)
The base-load current
I
L
is based on the duty cycle for low overload (LO).
3)
The base-load current
I
H
is based on the duty cycle for high overload
(HO).
4)
The input current depends on the motor load and line impedance and
applies for a line impedance corresponding to
u
K
= 1 %. The rated input
currents apply for a load at rated power (based on
I
rated
) – these current
values are specified on the rating plate.
5)
10 ms value from current-time characteristic for reliable tripping of installed
protection devices. If the minimum short-circuit current is not reached, the
tripping time of the fuses is increased, which can lead to damage.
© Siemens AG 2017