SIEMENS
SINAMICS DCM
Accessories and supplementary components
Commutating reactors
4/21
Siemens D 23.1 · 2014
4
■
Selection and ordering data
(continued)
1)
Note:
Commutating reactors with
u
K
= 2 % are available on request. A
limited tolerance range is also possible for parallel connections.
Three-phase commutating reactors,
u
K
= 4 %
AC rated
current
Inductance
Copper losses
Total losses
Short-circuit
current rating
(SCCR)
Weight
Rated
insulation
voltage
Article No.
A
mH
W
W
kA
kg
V
Rated voltage 690 V
598
0.085
388.2
562.1
55 (200 ms)
108.9
1000
6RX1800-4KK00
631
0.080
402.0
586.4
75(200毫秒)
113.3
1000
6RX1800-4KK01
789
0.064
362.7
564.6
75(200毫秒)
141.9
1000
6RX1800-4KK02
830
0.061
350.7
561.4
75(200毫秒)
153.4
1000
6RX1800-4KK03
1245
0.041
505.2
845.7
75(200毫秒)
169.7
1000
6RX1800-4KK04
1577
0.032
716.8
1093.8
75(200毫秒)
226.1
1000
6RX1800-4KK05
1660
0.031
596.0
1011.8
75(200毫秒)
257.2
1000
6RX1800-4KK06
2158
0.024
484.8
1185.6
75(200毫秒)
360.2
1000
6RX1800-4KK07
Rated voltage 830 V
789
0.077
312.0
532.1
75(200毫秒)
205.2
1000
6RX1800-4LK00
1245
0.049
692.4
1061.9
75(200毫秒)
222.4
1000
6RX1800-4LK01
1577
0.039
479.4
1059.6
75(200毫秒)
308.5
1000
6RX1800-4LK02
1826
0.033
585.6
1269.0
75(200毫秒)
372.5
1000
6RX1800-4LK03
Rated voltage 950 V
1826
0.038
534.9
1303.5
75(200毫秒)
399.7
1000
6RX1800-4MK00
Single-phase commutating reactors,
u
K
= 4 %
AC rated
current
Inductance
Copper losses
Total losses
Short-circuit
current rating
(SCCR)
Weight
Rated
insulation
voltage
Article No.
A
mH
W
W
kA
kg
V
Rated voltage 400 V
3
16.98
3
5
0.8 (20 ms)
0.7
600
6RX1800-4DE00
5
10.19
5
7
0.8 (20 ms)
1.5
600
6RX1800-4DE01
10
5.090
7
12
2 (20 ms)
2.0
600
6RX1800-4DE02
15
3.400
8
17
2 (20 ms)
2.3
600
6RX1800-4DE03
25
2.040
8
29
6(20 ms)
3.0
600
6RX1800-4DE04
30
1.700
10
30
6(20 ms)
3.8
600
6RX1800-4DE05
40
1.270
9
49
10 (20 ms)
5.2
600
6RX1800-4DE06
85
0.600
13
67
15 (20 ms)
9.6
600
6RX1800-4DE07
1)
All commutating reactors with rated voltages
V
N
≤
600 V to UL
© Siemens AG 2014