SIEMENS
7/121
Siemens IC 10 · 2017
* You can order this quantity or a multiple thereof.
插图是近似的。
Overload Relays
SIRIUS 3RB2 Electronic Overload Relays
3RB22, 3RB23 for high-feature applications
7
Function expansion modules for 3RB22 and 3RB23 overload relays (evaluation modules)
1)
The analog signal 4 mA up to 20 mA DC can be used for operating rotary
coil instruments or for feeding into analog inputs of programmable logic
controllers.
2)
The following information on ground-fault protection refers to sinusoidal
residual currents at 50/60 Hz:
-
With a motor current of between 0.3 and 2 times the current setting
I
e,
the
unit will trip at a ground-fault current equal to 30 % of the current setting.
-
With a motor current of between 2 and 8 times the current setting
I
e,
the
unit will trip at a ground-fault current equal to 15 % of the current setting.
-
The response delay amounts to between 0.5 s and 1 s.
Note:
Analog input modules, e.g. SM 331, must be configured for
4-wire measuring transducers. In this case the analog input
module must not supply current to the analog output of the
3RB22/3RB23 relay.
Size
contactor
Version
For
overload
relays
SD
Article No.
Price
per PU
PU
(UNIT,
SET, M)
PS*
PG
d
Sizes S00 to S12
For plugging into evaluation module
(1 unit)
3RB2985-2..1
S00 ... S12
Analog Basic 1 modules
1)
Analog output 4 ... 20 mA DC,
with overload warning
3RB22,
3RB23
}
3RB2985-2AA0
1
1 unit
41F
Analog Basic 1 GF modules
1)2)
Analog output 4 ... 20 mA DC,
与内部接地故障检测和
overload warning
3RB22,
3RB23
}
3RB2985-2AA1
1
1 unit
41F
Analog Basic 2 GF modules
1)2)
Analog output 4 ... 20 mA DC,
与内部接地故障检测和
ground-fault signal
3RB22,
3RB23
}
3RB2985-2AB1
1
1 unit
41F
Basic 1 GF modules
2)
与内部接地故障检测和
overload warning
3RB22,
3RB23
}
3RB2985-2CA1
1
1 unit
41F
Basic 2 GF modules
2)
与内部接地故障检测和
ground-fault signal
3RB22,
3RB23
}
3RB2985-2CB1
1
1 unit
41F
© Siemens AG 2016