SIEMENS
3/167
Siemens IK PI · 2015
PROFIBUS
Communication for SIMATIC S7-300
CP 342-5
3
■
具体的技术ations
Article No.
6GK7342-5DA03-0XE0
Product-type designation
CP 342-5
Transmission rate
Transmission rate at interface 1 in
accordance with PROFIBUS
9.6 kbit/s … 12 Mbit/s
Interfaces
Number of electrical connections
• at interface 1 in accordance
with PROFIBUS
1
• for power supply
1
Design of electrical connection
• at interface 1 in accordance
with PROFIBUS
9-pin Sub-D socket (RS485)
• for power supply
4-pin terminal strip
Supply voltage, current
consumption, power loss
Type of supply voltage
DC
Supply voltage
• 1 from backplane bus
5 V
• external
24 V
Relative positive tolerance at 24 V
with DC
20 %
Relative negative tolerance at 24 V
with DC
15 %
Consumed current
• from backplane bus at 5 V
for DC Typical
0.15 A
• from external supply voltage
at 24 V with DC
- typical
0.25 A
- maximum
-
Resistive loss
6.75 W
Permitted ambient conditions
Ambient temperature
• during operating
0 … 60 °C
• during storage
-40 … +70 °C
• during transport
-40 … +70 °C
• Comment
-
Relative humidity at 25 °C
without condensation during
operating maximum
95 %
保护类IP
IP20
Design, dimensions and weight
Module format
Compact module S7-300 single width
Width
40 mm
Height
125 mm
Depth
120 mm
Net weight
0.3 kg
Product properties, functions,
components
general
Number of modules
• per CPU maximum
4
• note
-
Performance data
Performance data
open communication
Number of possible connections for
open communication by means of
SEND/RECEIVE blocks maximum
16
Data volume as user data per
connection for open communication
by means of SEND/RECEIVE blocks
maximum
240 byte
Performance data
PROFIBUS DP
Service as DP master DPV0
Yes
Number of DP slaves on DP master
usable
124
Amount of data
• of the address area of the inputs
as DP master overall
2 160 byte
• of the address area of the outputs
as DP master overall
2 160 byte
• of the address area of the inputs
per DP slave
244 byte
• of the address area of the outputs
per DP slave
244 byte
•
of the address area of the diagnostic
data per DP slave
240 byte
Service as DP slave
• DPV0
Yes
• DPV1
-
Amount of data
• of the address area of the inputs
as DP slave overall
240 byte
• of the address area of the outputs
as DP slave overall
240 byte
Performance data
S7 communication
Number of possible connections for
S7 communication
• maximum
16
• with PG connections maximum
-
• with PG/OP connections maximum
-
• note
-
Performance data
multi-protocol mode
Number of active connections
with multi-protocol mode
• without DP maximum
32
• with DP maximum
28
Product functions
management,
configuration
Configuration software required
STEP 7 V5.1 SP2 or higher/
STEP 7 Professional V12 (TIA Portal)
or higher
Article No.
6GK7342-5DA03-0XE0
Product-type designation
CP 342-5
© Siemens AG 2014