Technical specifications
(continued)
PROFINET/Industrial Ethernet
SIMATIC ET 200eco
ET 200eco PN
6ES7145-6HD00-0AB0
Analog output modules
4 AA U/I;
4 x M12
General information
Vendor identification (VendorID)
002AH
Device identifier (DeviceID)
0306H
Supply voltage
24 V DC
Yes
permissible range, lower limit (DC)
20.4 V
permissible range, upper limit (DC)
28.8 V
Reverse polarity protection
Yes
Input current
Current consumption, typ.
280 mA
Encoder supply
Number of outputs
4
24 V encoder supply
• short-circuit protection
Yes; Electronic at 1.4 A
• Output current, max.
1 A
Power losses
Power loss, typ.
5.5 W
Analog outputs
Number of analog outputs
4
Voltage output,
short-circuit protection
Yes
Voltage output, short-circuit current,
max.
30 mA
Current output, no-load voltage,
max.
20 V
Output ranges, voltage
• 0 to 10 V
Yes
• 1 to 5 V
Yes
• -10 to +10 V
Yes
Output ranges, current
• 0 to 20 mA
Yes
• -20 to +20 mA
Yes
• 4 to 20 mA
Yes
Connection of actuators
•为双线式电压输出
connection
Yes
• for current output two-wire
connection
Yes
Load impedance
(in rated range of output)
• with voltage outputs, min.
1 k
• with voltage outputs,
capacitive load, max.
1 μF
• with current outputs, max.
600
• with current outputs,
inductive load, max.
1 mH
Destruction limits against externally
applied voltages and currents
• Voltages at the outputs towards
MANA
28.8 V permanent,
35 V for max. 500 ms
Cable length
• Cable length, shielded, max.
30 m
Analog value creation
Analog value display
SIMATIC S7 format
Measurement principle
Resistor network
Integrations and conversion time/res-
olution per channel
• Resolution (incl. overrange)
15 bits + sign
• Conversion time (per channel)
1 ms
Settling time
• for resistive load
2 ms
• for capacitive load
1.8 ms
• for inductive load
2 ms
Errors/accuracies
Output ripple
(based on output area,
bandwidth 0 to 50 kHz), (+/-)
U: ±0.6 mVrms;
I: ±0.4 nArms
Linearity error
(relative to output range), (+/-)
0.02%
Temperature error
(relative to output range), (+/-)
U: 0.001%/°C;
I: 0.0025%/°C
Crosstalk between the outputs, min.
70 dB
Repeat accuracy in steady state at
25 °C (relative to output area), (+/-)
0.008 %
Interfaces
Transmission procedure
100BASE-TX
Transmission rate, max.
100 Mbit/s
Supports protocol for PROFINET IO
• Number of PROFINET interfaces
1
• Autocrossing
Yes
• Automatic detection
of transmission speed
Yes
• Integrated switch
Yes
• PROFINET IO Device
-
IRT with the option "high flexibility"
supported
Yes
-
Prioritized startup
Yes
Protocols
Supports protocol for PROFINET IO
Yes
PROFINET CBA
No
Supports protocol for PROFIsafe
No
Protocols (Ethernet)
• SNMP
Yes
• DCP
Yes
• LLDP
Yes
• ping
Yes
• ARP
Yes
6ES7145-6HD00-0AB0
Analog output modules
4 AA U/I;
4 x M12
© Siemens AG 2014