SIEMENS
2/707
Siemens IK PI · 2015
PROFINET/Industrial Ethernet
SIMATIC PCS 7 process control systems
ET 200M for SIMATIC PCS 7
Interface Modules
2
■
Overview
我153 - 2高的特性interface module for PROFIBUS connection
Interface module for the PROFIBUS connection
The IM 153-2 High Feature interface module (electrical
PROFIBUS DP transmission mode) is available for connecting
the ET 200M remote I/O station to the PROFIBUS DP fieldbus.
Depending on the fieldbus configuration (single/redundant),
the ET 200M remote I/O station can be connected via one single
or two redundant interface modules.
IM 153-4 High Feature interface module for PROFINET connection
Interface module for PROFINET connection
The IM 153-4 PN High Feature interface module is used to
connect the ET 200M remote I/O station to PROFINET via copper
cables (RJ45). It autonomously handles communication
between the I/O modules and the higher-level PROFINET I/O
controller.
■
Function
我153 - 2高的特性
The IM 153-2 High Feature supports the following functions:
•
HART configuring of intelligent field devices
•
Configuration of ET 200M I/Os in RUN mode of the automation
system
•
Connection to redundant automation systems
•
Use of ET 200M function modules (controller and counter
modules)
•
Operation of up to 12 I/O modules per remote I/O station
•
Time stamping (SOE) with the safety-related SM 326F digital
input module (F-DI24)
•
Transmission of additional values with HART secondary
variables of the HART SM 331 and SM 332 analog modules
(up to 4 per channel or up to 8 per module)
IM 153-4 PN High Feature
•
Integrated 2-port switch
•
Baud rate 10 Mbps / 100 Mbps (Autonegotiation/Full Duplex)
•
Operation of up to 12 I/O modules per remote I/O station
•
I&M functions in accordance with PROFIBUS International
Guidelines, order no. 3.502, version V1.1
Note:
In order to be able to use the hot swapping function, use of
the active bus module and the mounting rail for hot swapping is
necessary (see under the following section "Accessories").
■
Ordering data
Article No.
Interface module for the PROFIBUS connection
我153 - 2高的特性
Slave interface module for connec-
tion of an ET 200M station to
PROFIBUS DP, with time stamp
(accuracy 1 ms), support of HART
functionality, F modules, FM mod-
ules, "Configuration in RUN" func-
tion; also for use in redundant
systems
6ES7153-2BA02-0XB0
Interface module for PROFINET connection
IM 153-4 PN High Feature
Interface for connecting an ET
200M station to PROFINET
6ES7153-4BA00-0XB0
© Siemens AG 2014