SIEMENS
2/682
Siemens IK PI · 2015
PROFINET/Industrial Ethernet
SIMATIC PCS 7 process control systems
AS 410 modular systems
2
■
Technical specifications
■
Accessories
Backup batteries
Lithium backup batteries of type AA with 2.3 Ah are used in the
power supply modules of all SIMATIC PCS 7 automation systems
of the S7-400 range (AS bundles). Since lithium batteries are
easily inflammable, more rigorous transport and storage regula-
tions apply to them.
为了避免对这些更r包igorous trans-
port and storage regulations, the backup batteries must be
ordered and delivered separately (order no. 6ES7971-0BA00).
The following backup batteries are required depending on the
configuration of the AS bundles:
•
SIMATIC PCS 7 AS Single Station with
- 1 power supply module: 2 units
- 2 redundant power supply modules: 4 units
•
SIMATIC PCS 7 AS Redundancy Station with
- 2 power supply modules: 4 units
- 2 x 2 redundant power supply modules: 8 units
CPU 410-5H Process Automation
General information
Firmware version
V8.0
Engineering with
SIMATIC PCS 7 V8.0+SP1 +
HUP CPU 410-5H
Degree of protection
IP20
Version
Conformal coating
Power supply
Supply voltage
5 V DC from SV system
Input current
• From backplane bus, 5 V DC max.
1.7 A
• From interface 5 V DC, max.
90 mA
Power loss, typical
7.5 W
内存
RAM
• For program
16 MB
• For data
16 MB
Load memory, integrated
48 MB
Buffering with battery
Yes, all data
CPU performance
Clock
450 MHz (multiprocessor system)
Average processing time
of APL typicals
Approx. 110 μs
PCS 7 process objects, can be set
with system expansion card
Up to approx. 2 600
Process tasks
Cyclic interrupts
(can be set from 10 ms to 5 s)
9
I/O
Total number of I/Os
Approx. 7 500 (16 KB inputs/outputs)
Number of I/Os per DP interface
Approx. 3 800 (8 KB inputs/outputs)
Number of I/Os per PN interface
Approx. 3 800 (8 KB inputs/outputs)
Communication
Number of S7 connections
120
Alarm_8P
10 000 (max. 80 000 messages)
Interfaces
• X1: PROFIBUS DP
1 x up to 12 Mbps, 9-pin Sub-D
socket
• X5: PROFINET IO with 2 ports
2 x 10/100 Mbps, RJ45
• X8: Service
2 x RJ45
• IF1: Sync module slot
(redundant systems)
Sync module 1
• IF2: Sync module slot
(redundant systems)
Sync module 2
Electromagnetic compatibility
(EMC)
Emission of radio interference
acc. to EN 55011
Limit class A, for use in industrial
areas
气候条件
Temperature
• Operation
0 ... 60 °C
Relative humidity
• Operation
0 to 95%, without condensation
Standards, specifications,
approvals
CE mark
Yes
cULus
Yes
CSA approval
Yes
FM approval
Yes
ATEX approval
Yes
Dimensions and weights
Dimensions (W x H x D in mm)
50 x 290 x 219
Weight
approx. 1.1 kg
CPU 410-5H Process Automation
© Siemens AG 2014